OCH790 _46
1508 (EF): 4-way valve trouble in heating mode
Abnormal points and detection methods
4-way valve does not operate during heating operation.
Any of the following temperature conditions is satisfied for
3 minutes or more during heating operation
TH22j−TH21j ≤ −10°C [−18°F]
TH23j−TH21j ≤ −10°C [−18°F]
TH22j ≤ 3°C [37.4°F]
TH23j ≤ 3°C [37.4°F]
Note:
•
For indoor unit, the abnormality is detected if an operating unit satisfies
the condition.
Causes and checkpoints
•
4-way valve failure
•
Disconnection or failure of 4-way valve coil
• Clogged drain pipe
• Disconnection or loose connection of connectors
•
Malfunction of input circuit on outdoor multi controller
circuit board
•
Defective outdoor power circuit board
TH21:
Indoor intake temperature thermistor (RT11 or TH1)
TH22:
Indoor liquid pipe temperature thermistor (RT13 or TH2)
TH23:
Indoor gas pipe temperature thermistor (TH-A to E)
Diagnosis of failure
Reconnect the connector or connect it tightly.
Disconnect the connector for outdoor multi
controller circuit board or 4-way valve coil to
check the resistance.
Replace the 4-way valve coil.
Replace the outdoor multi controller circuit
board.
Check the voltage and appearance of the
outdoor multi controller circuit board.
Replace the 4-way valve.
Refer to ''How to check the parts'' for ohm values.
Is the connector for outdoor multi
controller circuit board or 4-way valve
coil disconnected or loose?
Is the resistance detected?
Is the detected voltage normal?
Is it free from any trace of over-heat-
ing or burning?
Yes
No
No
No
Yes
Yes