OCH790 _64
5300 (UH): Current sensor trouble
Abnormal points and detection methods
The detected current sensor input value (primary current)
during compressor operation is outside the specified
range.
Causes and checkpoints
•
Decrease/Trouble of power supply voltage
•
Disconnection of compressor wiring
•
Input sensor trouble on outdoor power circuit board
Diagnosis of failure
Condition 1:
Model
Error detecting condition
1-phase
model
34 A or more for 10 consecutive
seconds, or 38 A or more
The power supply voltage is decreased or
abnormal.
Check the power supply facility.
Connect the compressor wiring properly.
Replace the outdoor power circuit board
(Malfunction of current sensor circuit).
Check the input current at the time of abnormal
stop.
Check the compressor wiring for disconnection
or looseness.
Does it satisfy the condition 1 in the
lower right? *
Is there any abnormality such as
disconnection or looseness?
Yes
No
No
Yes
*
Applicable only for single phase model
Содержание CITY MULTI PUMY-P112VKM6