![Mitsubishi Electric AE-200A Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/mitsubishi-electric/ae-200a/ae-200a_instruction-book_1810107046.webp)
46
WT07996X02
[5] HWHP (CAHV, CRHV) unit group
Item
Operation method
Description
ON/OFF
Select [ON] or
[OFF].
Turns on or off the units.
Operation
mode
Select an operation
mode.
Click the desired operation mode.
[Heating], [Heating ECO], [Hot Water], [Anti-freeze]
Set
temperature
Adjust the set
temperature with
the
buttons.
The settable temperature ranges depend on the operation mode and the unit model.
Schedule
Select [Available] or
[Not Available].
Enables/Disables the schedules.
Note: When [Not Available] is set, the scheduled operations are disabled even if
schedules are set.
Hold
Select [ON] or
[OFF].
Enables/Disables the Hold function. When the Hold function is enabled, the
scheduled operations are disabled.
Note: The operations that have been scheduled on the remote controller will also be
disabled.
Note: [Hold type] can be specified in the [Advanced] screen in the initial settings.
Refer to the Instruction Book (Initial Settings) for details.
Note: The Hold function can be used on the AE-200A/AE-50A/EW-50A, but not on the
AE-200E/AE-50E/EW-50E.
Fan Mode
Select [Normal] or
[Snow].
This item will appear only on the operation settings screen for HWHP (CAHV) unit
groups.
The fan can be set to keep rotating even while the unit is stopped to avoid snow
accumulation on the fan guard during the winter.
Select [Normal] to stop the fan while the unit is stopped. Select [Snow] to operate the
fan even while the unit is stopped.
Note: The fan mode for CRHV units cannot be operated.
Prohibit
Remote
Controller
Operation
Click the operation
item to switch the
setting between
“Prohibit” and
“Permit”.
The following operations or setting change can be prohibited from the local remote
controllers and when the Integrated Centralized Control Web is logged in with
general user privileges: ON/OFF, Operation mode, and Set temperature.
: Permit
: Prohibit
Send
Click [Send].
Click to reflect the changes made and return to the group list.
Close
Click [Close].
Click to return to the group list without making any changes.
Close
Click to close the settings
screen without making any
changes.
Send
Click to reflect
the changes
made.
Close
Click to close the settings
screen without making any
changes.
Send
Click to reflect the
changes made.
Group name
ON/OFF
Operation
mode
Set temperature
Hold
Schedule
Prohibit Remote
Controller Operation
Fan Mode