13
WT07996X02
Note: When connecting an AE-200/AE-50/EW-50 to an existing LAN, consult the system administrator to decide the IP addresses.
Note: When using an AE-200/AE-50/EW-50-dedicated LAN, it is recommended that the AE-200 unit and the EW-50 unit (only when
used alone) be assigned an IP address between the range [192.168.1.1] and [192.168.1.40], and the expansion controller
AE-50/EW-50 unit be assigned an IP address between the range [192.168.1.211] and [192.168.1.249].
[2] Floor settings
Use Initial Setting Tool to configure the floor settings of Integrated Centralized Control Web.
The configured settings are displayed in Integrated Centralized Control Web.
(1) In [Floor Settings] > [Floor for Integrated Centralized Control Web] of Initial Setting Tool, set the floor names
and floor number configuration displayed on the home screen of Integrated Centralized Control Web.
(2) In [Floor Settings] > [Floor Layout for Integrated Centralized Control Web], set the floor layout diagram and
icon locations.
Setting image 1
Procedure 1
Make settings of floors and floor names
on the “Floor for Integrated Centralized
Control Web” setting screen.
Setting image 2
Procedure 2
Make settings of floor layouts and
icon locations on the “Floor Layout for
Integrated Centralized Control Web”
setting screen.
General descriptions
Chapter 1