10
WIRING
*1
Remove the jumper between P1 and P/+ to connect the DC reactor.
*2
The function of these terminals can be changed using the Input terminal function selection (
Pr.178 to Pr.179
). (Refer to the FR-E800
Instruction Manual (Function).)
*3
The initial setting varies depending on the specification.
*4
Terminal input specifications can be changed by analog input specification switchover (
Pr.73, Pr.267
). To input voltage, set the voltage/
current input selection switch to "V". To input current, set the switch to "I". The initial setting varies depending on the specification. (Refer to
the FR-E800 Instruction Manual (Function).)
*5
It is recommended to use 2 W 1 k
Ω
when the frequency setting signal is changed frequently.
*6
The FR-E820-0008(0.1K), FR-E820-0015(0.2K), FR-E820S-0008(0.1K), and FR-E820S-0015(0.2K) are not equipped with brake transistors.
*7
Brake resistor (FR-ABR, MRS, MYS)
Install a thermal relay to prevent overheating and damage of brake resistors. (A brake resistor cannot be connected to the FR-E820-
0008(0.1K), FR-E820-0015(0.2K), FR-E820S-0008(0.1K), and FR-E820S-0015(0.2K).) (Refer to Instruction Manual (Connection))
*8
The function of these terminals can be changed using the
Pr.192 ABC terminal function selection
.
CAUTION
l
To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, keep the cables of the
main circuit for input and output separated.
l
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause a fault, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter.
l
Set the switches of the voltage/current input selection switch assembly correctly. Incorrect setting may cause a fault, failure or malfunction.
l
The output of the single-phase power input model is three-phase 200 V.