43
PARAMETER LIST
74
Input filter time
constant
0 to 8
1
75
Reset selection/
disconnected PU
detection/PU stop
selection
[E800(-E)]
0 to 3, 14 to 17
[E800-SCE]
0 to 3, 14 to 17,
10000 to 10003,
10014 to 10017
[E800(-E)]
14
[E800-SCE]
10014
Reset selection
0, 1
0
Disconnected PU
detection [E800]
PU stop selection
1
Reset limit
[E800-SCE]
0, 10
[E800-SCE]
[E800(-E)]
0
[E800-SCE]
10
77
Parameter write
selection
0 to 2
0
78
Reverse rotation
prevention selection
0 to 2
0
79
Operation mode
selection
0 to 4, 6, 7
0
80
Motor capacity
0.1 to 30 kW,
9999
9999
81
Number of motor
poles
2, 4, 6, 8, 10,
12, 9999
9999
82
Motor excitation
current
0 to 500 A, 9999
9999
83
Rated motor voltage
0 to 1000 V
[200 V
class]
200 V
[400 V
class]
400 V
[575 V
class]
575 V
84
Rated motor
frequency
10 to 400 Hz,
9999
9999
89
Speed control gain
(Advanced magnetic
flux vector)
0% to 200%,
9999
9999
90
Motor constant (R1)
0 to 50
Ω
, 9999
9999
91
Motor constant (R2)
0 to 50
Ω
, 9999
9999
92
Motor constant (L1)/
d-axis inductance
(Ld)
0 to 6000 mH,
9999
9999
93
Motor constant (L2)/
q-axis inductance
(Lq)
0 to 6000 mH,
9999
9999
94
Motor constant (X)
0% to 100%,
9999
9999
95
Online auto tuning
selection
0, 1
0
96
Auto tuning setting/
status
0, 1, 11
0
Parameter 100 to 99
Para-
meter
Name
Setting Range
Initial
Value
*1
117
PU communication
station number
[E800]
0 to 31
0
118
PU communication
speed [E800]
48, 96, 192,
384, 576, 768,
1152
192
Para-
meter
Name
Setting Range
Initial
Value
*1
Simple
Simple
Simple
119
PU communication
stop bit length / data
length [E800]
0, 1, 10, 11
1
PU communication
data length [E800]
0, 1
0
PU communication
stop bit length [E800]
0, 1
1
120
PU communication
parity check [E800]
0 to 2
2
121
PU communication
retry count [E800]
0 to 10, 9999
1
122
PU communication
check time interval
[E800]
0, 0.1 to 999.8 s,
9999
0
123
PU communication
waiting time setting
[E800]
0 to 150 ms,
9999
9999
124
PU communication
CR/LF selection
[E800]
0 to 2
1
125
Terminal 2 frequency
setting gain
frequency
0 to 590 Hz
Gr.1: 60 Hz
Gr.2: 50 Hz
126
Terminal 4 frequency
setting gain
frequency
0 to 590 Hz
Gr.1: 60 Hz
Gr.2: 50 Hz
127
PID control
automatic
switchover
frequency
0 to 590 Hz,
9999
9999
128
PID action selection
0, 20, 21, 40 to
43, 50, 51, 60,
61, 1000, 1001,
1010, 1011,
2000, 2001,
2010, 2011
0
129
PID proportional
band
0.1% to 1000%,
9999
100%
130
PID integral time
0.1 to 3600 s,
9999
1 s
131
PID upper limit
0% to 100%,
9999
9999
132
PID lower limit
0% to 100%,
9999
9999
133
PID action set point
0% to 100%,
9999
9999
134
PID differential time
0.01 to 10 s,
9999
9999
145
PU display language
selection [E800]
0 to 7
—
147
Acceleration/
deceleration time
switching frequency
0 to 590 Hz,
9999
9999
150
Output current
detection level
0% to 400%
150%
151
Output current
detection signal
delay time
0 to 10 s
0 s
152
Zero current
detection level
0% to 400%
5%
153
Zero current
detection time
0 to 10 s
0.5 s
154
Voltage reduction
selection during stall
prevention operation
1, 11
1
156
Stall prevention
operation selection
0 to 31, 100,
101
0
Para-
meter
Name
Setting Range
Initial
Value
*1
Simple
Simple
Simple
Simple
Simple
Simple