Electric Shock Prevention

Fire Prevention

This section is specifically about safety matters

Do not attempt to install, operate, maintain or inspect the inverter until you have read through this Installation Guideline and appended
documents carefully and can use the equipment correctly. Do not use the inverter until you have a full knowledge of the equipment,
safety information and instructions.
Installation, operation, maintenance and inspection must be performed by qualified personnel. Here, qualified personnel means person-
nel who meets all the conditions below.

l

A person who took a proper engineering training. Please note if you can take a proper engineering training at your local Mitsubishi Electric

office. Such training may be available at your local Mitsubishi Electric office. Contact your local sales office for schedules and locations.

l

A person who can access operating manuals for the protective devices (e.g. light curtain) connected to the safety control system. 

A person who has read and familiarized himself/herself with the manuals.

In this Installation Guideline, the safety instruction levels are classified into "WARNING" and "CAUTION".

Assumes that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

Assumes that incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may
cause physical damage only.

Note that even the 

level may lead to a serious consequence according to conditions. Please follow strictly the instructions

of both levels because they are important to personnel safety.

l

While power is on or when the inverter is running, do not open the front cover. Otherwise you may get an electric shock.

l

Do not run the inverter with the front cover removed. Otherwise, you may access the exposed high-voltage terminals or the charging part

of the circuitry and get an electric shock.

l

Even if power is off, do not remove the front cover except for wiring or periodic inspection.You may access the charged inverter circuits

and get an electric shock.

l

Before starting wiring or inspection, check to make sure that the LED display of the operation panel is off, wait for at least 10 minutes after

the power supply has been switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged

with high voltage for some time after power off and it is dangerous.

l

This inverter must be earthed. Earthing must conform to the requirements of national and local safety regulations and electrical codes

(JIS, NEC section 250, IEC 536 class 1 and other applicable standards). A neutral-point earthed power supply for 400V class inverter in

compliance with EN standard must be used.

l

Any person who is involved in the wiring or inspection of this equipment should be fully competent to do the work.

l

Always install the inverter before wiring. Otherwise, you may get an electric shock or be injured.

l

If your application requires by installation standards an RCD (residual current device) as up stream protection please select according to

DIN VDE 0100-530 as following:

Single phase inverter type A or B

Three phase inverter only type B

(Additional instructions on the use of a residual current device are contained on 

page 66

.)

l

Perform setting dial and key operations with dry hands to prevent an electric shock. Otherwise you may get an electric shock.

l

Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise you may get an electric shock.

l

Do not replace the cooling fan while power is on. It is dangerous to replace the cooling fan while power is on.

l

Do no

t touch the printed circuit board or handle the cables with wet hands. You may get an electric shock.

l

When measuring the main circuit capacitor capacity, the DC voltage is applied to the motor for 1s at powering OFF. Never touch the motor

terminal, etc. right after powering OFF to prevent an electric shock.

l

A PM motor is a synchronous motor with high-performance magnets embedded in the rotor. Motor terminals holds high-voltage while the

motor is running even after the inverter power is turned OFF. Before wiring or inspection, the motor must be confirmed to be stopped. In

an application, such as fan and blower, where the motor is driven by the load, a low-voltage manual motor starter must be connected at

the inverter's output side, and wiring and inspection must be performed while the motor starter is open. Otherwise you may get an electric

shock.

l

Mount the inverter to incombustible material. Install the inverter on a nonflammable wall without holes (so that nobody can touch the

inverter heatsink on the rear side, etc.). Mounting it to or near combustible material can cause a fire.

l

If the inverter has become faulty, switch off the inverter power. A continuous flow of large current could cause a fire.

l

Do not connect a resistor directly to the DC terminals P/+, N/–. This could cause a fire and destroy the inverter. 

l

The surface temperature of braking resistors can far exceed 100°C for brief periods. Make sure that there is adequate protection against

accidental contact and a safe distance is maintained to other units and system parts.

l

Be sure to perform daily and periodic inspections as specified in the Instruction Manual. If a product is used without any inspection, a

burst, breakage, or a fire may occur.

WARNING

CAUTION

CAUTION

WARNING

CAUTION

Содержание 800 Series

Страница 1: ...ILSAFE OF THE SYSTEM WHICH USES THE INVERTER 31 PRECAUTIONS FOR USE OF THE INVERTER 29 BASIC OPERATION 35 PARAMETER LIST 41 INVERTER FAULT AND ALARM INDICATIONS 55 SPECIFICATIONS 59 APPENDIX 65 Thank you for choosing this Mitsubishi Electric Inverter This Installation guideline and the enclosed CD ROM give handling information and precautions for use of this product Do not use this product until y...

Страница 2: ...as machinery or systems used in passenger transportation medical aerospace atomic power electric power or submarine repeating applications please contact your nearest Mitsubishi Electric sales representative l Although this product was manufactured under conditions of strict quality control you are strongly advised to install safety devices to prevent serious accidents when it is used in facilitie...

Страница 3: ... standards A neutral point earthed power supply for 400V class inverter in compliance with EN standard must be used l Any person who is involved in the wiring or inspection of this equipment should be fully competent to do the work l Always install the inverter before wiring Otherwise you may get an electric shock or be injured l If your application requires by installation standards an RCD residu...

Страница 4: ...or the installation at an altitude above 1000 m consider a 3 reduction in the rated current per 500 m increase in altitude l If halogen based materials fluorine chlorine bromine iodine etc infiltrate into a Mitsubishi Electric product the product will be damaged Halogen based materials are often included in fumigant which is used to sterilize or disinfect wooden packages When packaging prevent res...

Страница 5: ...ess surge voltage Surge voltage attributable to the wiring constants may occur at the motor terminals deteriorating the insulation of the motor l Use a motor designed for inverter operation The stress for motor windings is bigger than in line power supply l When parameter clear or all clear is performed set again the required parameters before starting operations Each parameter returns to the init...

Страница 6: ...ailure l Treat as industrial waste General instructions Many of the diagrams and drawings in instruction manuals show the inverter without a cover or partially open Never run the inverter in this status Always replace the cover and follow instruction manuals when operating the inverter For more details on the PM motor refer to the Instruction Manual of the PM motor CAUTION CAUTION ...

Страница 7: ...on type and the functional safety specification are shown Symbol Voltage class 2 200 V class 4 400 V class Symbol Description None Three phase input S Single phase input Symbol Description 0 1K to 22K Inverter ND rated capacity kW 0008 to 0900 Inverter ND rated current A Symbol Communication functional safety None Standard model RS 485 SIL2 PLd E Ethernet model Ethernet SIL2 PLd SCE Safety communi...

Страница 8: ...c fixed 4 Voltage terminal AM 50 Hz Source logic 5 Voltage terminal AM 60 Hz Sink logic PA Protocol group A CC Link IE TSN CC Link IE Field Network Basic MODBUS TCP EtherNet IP and BACnet IP 60 Hz Sink logic PB Protocol group B CC Link IE TSN CC Link IE Field Network Basic MODBUS TCP PROFINET 50 Hz Sink logic Source logic 1 Symbol Circuit board coating 1 Plated conductor None Without coating Witho...

Страница 9: ...ake such measures as to provide guides between the inverters since heat generated in the inverters in bottom row can increase the temperatures in the inverters in top row causing inverter failures 1 5 Environment Before installation check that the environment meets following specifications 1 Temperature applicable for a short time for example in transit 2 For installation at an altitude above 1000...

Страница 10: ...4 INSTALLATION AND INSTRUCTIONS ...

Страница 11: ...0VDC PU connector Connector for plug in option connection Analog signal output Relay output Fault output Running Frequency detection Open collector output common Sink source common Safety stop signal Safety monitor output Indicator Frequency meter etc Frequency setting potentiometer W 1 k 5 Open collector output 9 Relay output 8 Voltage current input switch Analog common Brake unit option Single p...

Страница 12: ...or cannot be connected to the FR E820 0008 0 1K FR E820 0015 0 2K FR E820S 0008 0 1K and FR E820S 0015 0 2K Refer to Instruction Manual Connection 8 The function of these terminals can be changed using the Pr 192 ABC terminal function selection 9 The function of these terminals can be changed using the Output terminal function selection Pr 190 or Pr 191 Refer to the FR E800 Instruction Manual Func...

Страница 13: ...tor Connector for plug in option connection Analog signal output Relay output Fault output Running Frequency detection Open collector output common Sink source common Safety stop signal Safety monitor output Indicator Frequency meter etc Frequency setting potentiometer W 1 k 5 Open collector output 9 Relay output 8 Voltage current input switch Analog common Brake unit option Single phase power inp...

Страница 14: ...or cannot be connected to the FR E820 0008 0 1K FR E820 0015 0 2K FR E820S 0008 0 1K and FR E820S 0015 0 2K Refer to Instruction Manual Connection 8 The function of these terminals can be changed using the Pr 192 ABC terminal function selection 9 The function of these terminals can be changed using the Output terminal function selection Pr 190 or Pr 191 Refer to the FR E800 Instruction Manual Func...

Страница 15: ...put Motor DC reactor FR HEL Earth Ground Jumper Single phase AC power supply Main circuit Control circuit Frequency setting signals Analog Terminal 4 input Current input Connector for plug in option connection Frequency setting potentiometer W 1 k 5 24VDC power supply Common for external power supply transistor Shorting wire Safety stop input Channel 1 Safety stop input Channel 2 Safety stop input...

Страница 16: ...resistor FR ABR MRS MYS Install a thermal relay to prevent overheating and damage of brake resistors A brake resistor cannot be connected to the FR E820 0008 0 1K FR E820 0015 0 2K FR E820S 0008 0 1K and FR E820S 0015 0 2K Refer to Instruction Manual Connection 8 The function of these terminals can be changed using the Pr 192 ABC terminal function selection CAUTION l To prevent a malfunction due t...

Страница 17: ...input Motor DC reactor FR HEL Earth Ground Jumper Single phase AC power supply Main circuit Control circuit Frequency setting signals Analog Terminal 4 input Current input Connector for plug in option connection Frequency setting potentiometer W 1 k 5 24VDC power supply Contact input common Shorting wire Safety stop input Channel 1 Safety stop input Channel 2 Safety stop input common Common for ex...

Страница 18: ...resistor FR ABR MRS MYS Install a thermal relay to prevent overheating and damage of brake resistors A brake resistor cannot be connected to the FR E820 0008 0 1K FR E820 0015 0 2K FR E820S 0008 0 1K and FR E820S 0015 0 2K Refer to Instruction Manual Connection 8 The function of these terminals can be changed using the Pr 192 ABC terminal function selection CAUTION l To prevent a malfunction due t...

Страница 19: ...ult output Relay output 6 Main circuit Control circuit Frequency setting signals Analog Terminal 4 input Current input Connector for plug in option connection Frequency setting potentiometer W 1 k 3 0 to 5VDC 4 to 20mADC 0 to 5VDC 0 to 20mADC 0 to 5VDC 0 to 10VDC Ethernet connector Voltage current input switch USB mini B connector Option connector Ethernet connector Safety communication function s...

Страница 20: ...esistor cannot be connected to the FR E820 0008 0 1K FR E820 0015 0 2K FR E820S 0008 0 1K and FR E820S 0015 0 2K Refer to Instruction Manual Connection 6 The function of these terminals can be changed using the Pr 192 ABC terminal function selection CAUTION l To prevent a malfunction due to noise keep the signal cables 10 cm or more away from the power cables Also keep the cables of the main circu...

Страница 21: ... T L3 S L2 M Earthing grounding terminal Motor Power supply Jumper N P PR R L1 S L2 T L3 M Motor Power supply Jumper Jumper Earthing grounding terminal N P PR R L1 S L2 T L3 M Jumper Motor Power supply Earthing grounding terminal R L1 S L2 T L3 N P PR M Motor Power supply Jumper Earthing grounding terminal Earthing grounding terminal R L1 S L2 T L3 N P PR M Motor Power supply Earthing grounding te...

Страница 22: ...inverter Doing so will damage the inverter Phase sequence needs not to be matched l Connect the motor to U V W At this time turning on the forward rotation switch signal rotates the motor in the clockwise direction when viewed from the motor shaft The phase sequence must be matched CAUTION l Cut off the same number of lugs as wires If parts where no wire is put through have been cut off 10 mm or m...

Страница 23: ...R E820 ã Terminal screw size 4 Tightening torque Nm Crimping Terminal Cable sizes HIV etc mm 1 AWG MCM 2 PVC etc mm 3 R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W P P1 Earth cable gauge R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W Earth cable gauge 0008 0 1K to 0050 0 75K M3 5 1 2 2 3 5 2 3 5 2 2 2 2 14 14 2 5 2 5 2 5 0080 1 5K 0110 2 2K M4 1 5 2 4 2 4 2 2 2 2 14 14 2 5 2 5 2 5 0175 3 7K M4 1 5 5 5 4 5 ...

Страница 24: ...n parentheses Applicable inverter type FR E840 ã Terminal screw size 4 Tightening torque Nm Crimping terminal Cable sizes HIV etc mm 1 AWG MCM 2 PVC etc mm 3 R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W P P1 Earth cable gauge R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W Earth cable gauge 0016 0 4K to 0095 3 7K M4 1 5 2 4 2 4 2 2 2 2 14 14 2 5 2 5 2 5 0120 5 5K M4 1 5 2 4 2 4 2 2 3 5 2 14 14 2 5 2 5 2 5 ...

Страница 25: ...erminal Cable sizes HIV etc mm 2 AWG MCM 3 PVC etc mm 4 R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W P P1 Earth cable gauge R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W Earth cable gauge 0008 0 1K to 0050 0 75K M3 5 1 2 2 3 5 2 3 5 2 2 2 2 14 14 2 5 2 5 2 5 0080 1 5K M4 1 5 2 4 2 4 2 2 2 2 14 14 2 5 2 5 2 5 0110 2 2K M4 1 5 5 5 4 5 5 4 3 5 3 5 3 5 3 5 12 12 4 4 4 0175 3 7K M4 1 5 5 5 4 5 5 4 5 5 5 5 5 5...

Страница 26: ...ses The line voltage drop can be calculated by the following formula Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop torque reduction in the low speed range Applicable inverter Type FR E840 ã Terminal screw size 1 Tightening torque Nm Crimping terminal Cable Sizes HIV etc mm 2 AWG MCM 3 PVC etc mm 4 R L1 S L2 T L3 U V W R L1 S L2 T L3...

Страница 27: ...m 100 m 200 m 200 m 500 m Shielded 1 1 kHz or lower 200 V 50 m 50 m 75 m 100 m 100 m 100 m 100 m 400 V 50 m 50 m 75 m 100 m 100 m 2 2 kHz or higher 200 V 10 m 25 m 50 m 75 m 100 m 100 m 100 m 400 V 10 m 25 m 50 m 75 m 100 m Wiring length 50 m or shorter Wiring length 50 to 100 m Wiring length longer than 100 m 14 5 kHz or lower 8 kHz or lower 2 kHz or lower CAUTION l Especially for long distance w...

Страница 28: ...Establishing adequate common single point earth ground system II shown in the following figure is allowed only in cases where the separate earth ground system I is not feasible Do not make inadequate common single point earth ground connection III As leakage currents containing many high frequency components flows into the earthing grounding cables of the inverter and peripheral devices including ...

Страница 29: ...ype inverter l Recommended cable gauge 0 3 to 0 75 mm2 Standard model AM type inverter l Recommended cable gauge 0 3 to 0 75 mm2 S1 S2 PC RUN FU SE RL RM RH SD MRS RES SD STF STR SO SOC 10 2 5 SD FM 4 A B C S1 S2 PC RUN FU SE RL RM RH SD MRS RES SD STF STR SO SOC 10 2 5 5 AM 4 A B C ...

Страница 30: ...f the wire and apply directly Insert the blade terminal or the single wire into a socket of the terminal 1 Strip off the sheath for the below length If the length of the sheath peeled is too long a short circuit may occur with neighbouring wires If the length is too short wires might come off Wire the stripped cable after twisting it to prevent it from becoming loose In addition do not solder it C...

Страница 31: ...umber Insulation product number Manufacturer Crimping tool product number 0 3 to 0 75 BT 0 75 11 VC 0 75 NICHIFU Co Ltd NH 69 3 Insert the wires into a socket When using a single wire or stranded wires without a blade terminal push the open close button all the way down with a flathead screwdriver and insert the wire CAUTION l Pulling out the wire forcefully without pushing the open close button a...

Страница 32: ...h the shield to the enclosure etc l Always apply a voltage to the alarm output terminals A1 B1 C1 A2 B2 C2 via a relay coil lamp etc l When a relay coil is connected to the output terminals use one with a surge absorbing function reflux diode When the voltage application direction is incorrect the inverter will be damaged Pay attention to the diode direction or other precautions to avoid incorrect...

Страница 33: ...ctric shock hazard install a magnetic contactor MC at the input side of the inverter Terminal symbol Terminal function description S1 1 Input terminal as the safety stop channel 1 Status of both the circuit between terminals S1 and PC and the circuit between terminals S2 and PC Open Safety stop is activated Shorted Safety stop is not activated S2 1 Input terminal as the safety stop channel 2 PC 1 ...

Страница 34: ...signal and SAFE2 signal has not been certified for compliance with safety standards For details refer to the FR E800 Instruction Manual Functional Safety Input power Internal safety circuit status Input terminal 1 2 Output terminal Output signal 8 9 10 Inverter operation enable signal Operation panel indication S1 S2 SO SAFE SAFE2 E SAF 6 SA 7 OFF OFF OFF OFF Output shutoff Safe state Not displaye...

Страница 35: ...inal function description SX1 Terminal functions can be selected using Pr S051 SX1 SX2 terminal function selection SX2 SY1 Terminal functions can be selected using Pr S055 SY1 SY2 terminal function selection SY2 SD Connect this terminal to the power supply common terminal of a transistor output open collector output device such as a programmable controller in the source logic to avoid malfunction ...

Страница 36: ...ion Manual of each communication option 7 The use of the SAFE signal and SAFE2 signal has not been certified for compliance with safety standards For details refer to the FR E800 SCE Instruction Manual Functional Safety E SAF indication 3 Status of safety related parts STO function status when the STO or SS1 command is input Inverter operating status SA indication 4 Output signal 5 6 7 SAFE SAFE2 ...

Страница 37: ...tput The ALM signal is assigned to terminals A B and C in the initial setting With this signal check that the inverter operates properly In addition negative logic can be set ON when the inverter is normal OFF when the fault occurs Checking the inverter operating status by using the Inverter operation ready signal output from the inverter b The Inverter operation ready RY signal is output when the...

Страница 38: ...verter s deceleration time Backup method which does not use the inverter Even if the interlock is provided by the inverter status signal enough failsafe is not ensured depending on the failure status of the inverter itself For example if an inverter CPU fails in a system interlocked with the inverter s Fault start and RUN signals no Fault signals will be output and the RUN signal will be kept ON b...

Страница 39: ...etc The inverter s output side has no short circuit or ground fault occurring A short circuit or ground fault on the inverter s output side may damage the inverter module Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by peripheral circuit inadequacy or an earth ground fault caused by wiring inadequacy or reduced motor insulati...

Страница 40: ...quency setting signal to fluctuate and the motor rotation speed to be unstable when changing the motor speed with analog signals the following countermeasures are effective Do not run the signal cables and power cables inverter I O cables in parallel with each other and do not bundle them Run the signal cables as far away as possible from the power cables inverter I O cables Use shielded cables In...

Страница 41: ... during inverter running ON During forward rotation operation Blinks slowly 1 4 second cycle During reverse rotation operation Blinks quickly 0 2 second cycle Operation is disabled although the start command is given 1 F Controlled motor type LED indicator ON when the inverter is set to control the PM motor The indicator blinks during test operation The indicator is OFF when the inverter controls ...

Страница 42: ... C Inverter operation mode LED indicator PU ON when the inverter is in the PU operation mode EXT ON when the inverter is in the External operation mode ON when the inverter in the initial setting is powered ON NET ON when the inverter is in the Network operation mode PU and EXT ON when the inverter is in the External PU combined operation mode 1 or 2 D Operation panel mode LED indicator MON ON or ...

Страница 43: ...hen Pr 161 0 initial setting refer to Instruction Manual Function K SET key Confirms each selection When this key is pressed during inverter operation the monitor item changes The monitor item on each screen can be changed according to the settings of Pr 52 Pr 774 to Pr 776 L RUN key Start command The direction of motor rotation depends on the Pr 40 setting M STOP RESET key Stops the operation com...

Страница 44: ... Frequency setting written and completed First screen Output frequency monitoring 2 Second screen Output current monitoring 2 Monitor Parameter setting Faults history PU operation mode Parameter clear Change the setting The present setting is displayed Parameter write completed All parameter clear Faults history clear Group parameter setting Automatic parameter setting Example Blinking Example Exa...

Страница 45: ...tting written and completed First screen Output frequency monitoring 2 Second screen Output current monitoring 2 Monitor Parameter setting Faults history PU operation mode Parameter clear Change the setting The present setting is displayed Parameter write completed All parameter clear Faults history clear Group parameter setting Automatic parameter setting Example Blinking Example Example Blinking...

Страница 46: ...40 BASIC OPERATION ...

Страница 47: ...FR E800 Function Manual for instruction codes for communication and availability of parameter copy Parameter clear and all clear Simple Simple Simple Parameter 0 to 99 Para meter Name Setting Range Initial Value 1 0 Torque boost 0 to 30 6 5 4 3 2 2 1 Maximum frequency 0 to 120 Hz 120 Hz 2 Minimum frequency 0 to 120 Hz 0 Hz 3 Base frequency 0 to 590 Hz Gr 1 60 Hz Gr 2 50 Hz 4 Multi speed setting hi...

Страница 48: ...etting Range Initial Value 1 52 Operation panel main monitor selection E800 E800 SC EPB 0 5 to 14 17 to 20 23 to 33 35 38 40 to 42 44 45 50 to 57 61 62 64 65 67 91 97 100 E800 SC EPA 0 5 to 14 17 to 20 23 to 33 35 38 40 to 42 44 45 50 to 57 61 62 64 65 67 83 91 97 100 0 53 Frequency rotation speed unit switchover 0 1 4 0 54 FM terminal function selection E800 1 1 to 3 5 to 14 17 18 21 24 32 33 50 ...

Страница 49: ...Simple Simple 119 PU communication stop bit length data length E800 0 1 10 11 1 PU communication data length E800 0 1 0 PU communication stop bit length E800 0 1 1 120 PU communication parity check E800 0 to 2 2 121 PU communication retry count E800 0 to 10 9999 1 122 PU communication check time interval E800 0 0 1 to 999 8 s 9999 0 123 PU communication waiting time setting E800 0 to 150 ms 9999 9...

Страница 50: ...43 46 47 50 51 62 65 to 67 72 74 76 87 to 89 92 9999 E800 SC E 0 to 4 8 13 to 15 18 23 24 26 27 30 37 42 43 46 47 50 51 72 74 76 87 to 89 92 9999 0 181 RM terminal function selection 1 182 RH terminal function selection 2 183 MRS terminal function selection 24 184 RES terminal function selection E800 62 E800 SC E 9999 Para meter Name Setting Range Initial Value 1 Simple Simple Simple 185 NET X1 in...

Страница 51: ...switchover 0 10 10 261 Power failure stop selection 0 to 2 0 Para meter Name Setting Range Initial Value 1 267 Terminal 4 input selection 0 to 2 0 268 Monitor decimal digits selection 0 1 9999 9999 269 Parameter for manufacturer setting Do not set 270 Stop on contact control selection 0 1 11 0 275 Stop on contact excitation current low speed scaling factor 0 to 300 9999 9999 276 PWM carrier freque...

Страница 52: ... 0 to 590 Hz 9999 9999 375 Faulty acceleration rate detection level 0 to 400 Hz 9999 9999 376 4 Encoder signal loss detection enable disable selection 0 1 0 390 setting reference frequency E800 SC EPA 1 to 590 Hz Gr 1 60 Hz Gr 2 Parameter 400 to 499 Para meter Name Setting Range Initial Value 1 414 PLC function operation selection 0 to 2 11 12 0 415 Inverter operation lock mode setting 0 1 0 420 C...

Страница 53: ... 0 to 9999 0 Para meter Name Setting Range Initial Value 1 Parameter 500 to 599 Para meter Name Setting Range Initial Value 1 502 Stop mode selection at communication error 0 to 2 6 0 503 Maintenance timer 0 1 to 9998 0 504 Maintenance timer warning output set time 0 to 9998 9999 9999 505 Speed setting reference 1 to 590 Hz Gr 1 60 Hz Gr 2 50 Hz 506 Display estimated main circuit capacitor residua...

Страница 54: ...operation frequency selection 0 1 0 Para meter Name Setting Range Initial Value 1 653 Speed smoothing control 0 to 200 0 654 Speed smoothing cutoff frequency 0 to 120 Hz 20 Hz 660 Increased magnetic excitation deceleration operation selection 0 1 0 661 Magnetic excitation increase rate 0 to 40 9999 9999 662 Increased magnetic excitation current level 0 to 200 100 665 Regeneration avoidance frequen...

Страница 55: ...92 3 Deceleration time in low speed range 0 to 3600 s 9999 9999 Para meter Name Setting Range Initial Value 1 Parameter 800 to 999 Para meter Name Setting Range Initial Value 1 800 Control method selection 0 to 5 9 10 to 12 19 20 40 40 801 Output limit level 0 to 400 9999 9999 802 Pre excitation selection 0 1 0 803 Constant output range torque characteristic selection 0 to 2 10 0 804 Torque comman...

Страница 56: ...to 400 150 880 Load inertia ratio 0 to 200 times 7 times 881 Speed feed forward gain 0 to 1000 0 Para meter Name Setting Range Initial Value 1 882 Regeneration avoidance operation selection 0 to 2 0 883 Regeneration avoidance operation level 300 to 1200 V 200 V class 400 V 400 V class 780 V 575 V class 944 V 885 Regeneration avoidance compensation frequency limit value 0 to 45 Hz 9999 6 Hz 886 Reg...

Страница 57: ...e 1 1103 3 Deceleration time at emergency stop 0 to 3600 s 5 s 1106 Torque monitor filter 0 to 5 s 9999 9999 1107 Running speed monitor filter 0 to 5 s 9999 9999 1108 Excitation current monitor filter 0 to 5 s 9999 9999 1124 Station number in inverter to inverter link E800 SC E 0 to 5 9999 9999 1125 Number of inverters in inverter to inverter link system E800 SC E 2 to 6 2 1150 to 1199 PLC functio...

Страница 58: ...erter identification enable disable selection E800 SC E 0 1 1 Para meter Name Setting Range Initial Value 1 Parameter 1400 to 1499 Para meter Name Setting Range Initial Value 1 1412 Motor induced voltage constant phi f exponent 0 to 2 9999 9999 1413 Second motor induced voltage constant phi f exponent 0 to 2 9999 9999 1424 Ethernet communication network number E800 SC E 1 to 239 1 1425 Ethernet co...

Страница 59: ...s maximum frequency 0 to 590 Hz Gr 1 60 Hz Gr 2 50 Hz 1487 Load characteristics minimum frequency 0 to 590 Hz 6 Hz Para meter Name Setting Range Initial Value 1 1488 Upper limit warning detection width 0 to 400 9999 20 1489 Lower limit warning detection width 0 to 400 9999 20 1490 Upper limit fault detection width 0 to 400 9999 9999 1491 Lower limit fault detection width 0 to 400 9999 9999 1492 Lo...

Страница 60: ... for more details 3 The set value is read written in 2 word 32 bit units when the PLC function is used for parameter reading writing 4 The setting is available only when a Vector control compatible option is installed 5 On the LCD operation panel used as the command source the parameter number in parentheses appears instead of that starting with the letter C 6 For the Ethernet model and the safety...

Страница 61: ...cation When a protective function is activated the operation panel displays a fault indication l Operation restart method While a protective function is activated the inverter output is kept shutoff Reset the inverter to restart the operation Inverter fault or alarm indications are categorized as follows l Error Message A message regarding operational fault or setting fault on the operation panel ...

Страница 62: ...FF status of the start signal must be confirmed before resetting the inverter fault Resetting inverter fault with the start signal ON restarts the motor suddenly This may cause injury ON OFF Inverter PC RES Operation panel indication Name Data code Error message HOLD Operation panel lock LOCD Password locked Er1 to Er4 Parameter write error Err Error Warning OLC Stall prevention overcurrent 1 H01 ...

Страница 63: ... HA0 E OP1 Communication option fault 161 HA1 E 16 User definition error by the PLC function 164 HA4 E 17 165 HA5 E 18 166 HA6 E 19 167 HA7 E 20 168 HA8 E PE Parameter storage device fault control circuit board 176 HB0 E PUE PU disconnection 177 HB1 E RET Retry count excess 178 HB2 Operation panel indication Name Data code Fault E PE2 Parameter storage device fault main circuit board 179 HB3 E CPU...

Страница 64: ...58 INVERTER FAULT AND ALARM INDICATIONS ...

Страница 65: ...a power supply that cannot resist the regenerative voltage energy is used connect a reverse current prevention diode in series Powering ON produces up to four times as large current as the inverter rated current Prepare a DC power supply resistant to the inrush current at power ON although an inrush current limit circuit is provided in the FR E800 series inverter The power capacity depends on the ...

Страница 66: ... resistant to the regenerative voltage energy When a power supply that cannot resist the regenerative voltage energy is used connect a reverse current prevention diode in series Powering ON produces up to four times as large current as the inverter rated current Prepare a DC power supply resistant to the inrush current at power ON although an inrush current limit circuit is provided in the FR E800...

Страница 67: ...option brake resistor for an operation with large regenerative power not available for the FR E820S 0008 0 1K and FR E820S 0015 0 2K The brake unit FR BU2 can be also used 6 The power supply capacity varies with the value of the input power impedance including those of the input reactor and cables 7 The value in parentheses is the rated output current when the low acoustic noise operation is perfo...

Страница 68: ...015 0 2K E FR E820S 0015 0 2K SCE FR E820S 0030 0 4K FR E820S 0030 0 4K E FR E820S 0030 0 4K SCE 142 5 FR E820S 0050 0 75K FR E820S 0050 0 75K E FR E820S 0050 0 75K SCE 108 96 135 FR E820S 0080 1 5K FR E820S 0080 1 5K E FR E820S 0080 1 5K SCE 161 FR E820S 0110 2 2K FR E820S 0110 2 2K E FR E820S 0110 2 2K SCE 140 128 142 5 W1 W H1 H D W1 W H1 H ø C ø C Standard model Ethernet model Safety communica...

Страница 69: ...E820 0600 15K E FR E820 0600 15K SCE FR E820 0760 18 5K FR E820 0760 18 5K E FR E820 0760 18 5K SCE 200 350 330 10 FR E820 0900 22K FR E820 0900 22K E FR E820 0900 22K SCE 400V class FR E840 0016 0 4K FR E840 0016 0 4K E FR E840 0016 0 4K SCE 108 96 128 118 129 5 5 FR E840 0026 0 75K FR E840 0026 0 75K E FR E840 0026 0 75K SCE FR E840 0040 1 5K FR E840 0040 1 5K E FR E840 0040 1 5K SCE 135 FR E840...

Страница 70: ...64 SPECIFICATIONS ...

Страница 71: ...twork which supplies domestic premises When using the inverter in a residential area take appropriate measures and ensure the conformity of the inverter used in the residential area l Radio frequency interference is expected if used on such a network l The installer shall provide a guide for installation and use including recommended mitigation devices NOTES l First environment Environment includi...

Страница 72: ...careful not to damage the threads For use as a product compliant with the Low Voltage Directive use PVC cable whose size is indicated on page 17 l Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard l This product can cause a DC current in the protective earthing conductor Where a residual current operated protective RCD or monitoring RCM device is u...

Страница 73: ...ional local code l Precautions for opening the branch circuit protective device WARNING The bus capacitor discharge time is 10 minutes Before starting wiring or inspection switch power off wait for more than 10 minutes and check for residual voltage between terminal P and N with a meter etc to avoid a hazard of electrical shock WARNING Operation of this product requires detailed installation and o...

Страница 74: ...00 V 40 A FR E840 0120 5 5K 0170 7 5K 170M1416 Bussmann 700 V 80 A FR E820 0110 2 2K 170M1414 170M1314 or 170M1364 Bussmann 700 V 50 A FR E840 0230 11K 170M1419 170M1319 or 170M1469 Bussmann 700 V 160 A FR E820 0175 3 7K 170M1416 170M1316 or 170M1366 Bussmann 700 V 80 A FR E840 0300 15K 170M1419 170M1319 or 170M1469 Bussmann 700 V 160 A FR E820 0240 5 5K 170M1418 170M1318 or 170M1368 Bussmann 700 ...

Страница 75: ...smann 700 V 200 A FR E820 0330 7 5K 170M1419 170M1319 or 170M1369 Bussmann 700 V 160 A FR E840 0440 22K 170M1421 170M1321 or 170M1471 Bussmann 700 V 250 A FR E820 0470 11 170M1420 170M1320 or 170M1370 Bussmann 700 V 200 A FR E820S 0008 0 1K 170M1408 Bussmann 700 V 10 A FR E820 0600 15K 170M1421 170M1321 or 170M1471 Bussmann 700 V 250 A FR E820S 0015 0 2K 170M1409 Bussmann 700 V 16 A FR E820 0760 1...

Страница 76: ...ng terminal is shown Inverter model Terminal screw size 1 Tightening torque N m Crimp terminal Cable gauge AWG R L1 S L2 T L3 U V W R L1 S L2 T L3 U V W FR E820 0008 0 1K to 0050 0 75K M3 5 1 2 2 3 5 2 3 5 14 14 FR E820 0080 1 5K M4 1 5 3 5 4 2 4 12 14 FR E820 0110 2 2K M4 1 5 5 5 4 2 4 10 14 FR E820 0175 3 7K M4 1 5 8 4 5 5 4 8 10 FR E820 0240 5 5K M5 2 5 8 5 8 5 8 8 FR E820 0330 7 5K M5 2 5 14 5...

Страница 77: ...nic thermal O L relay is reset to the initial value by the inverter s power reset or reset signal input Avoid unnecessary reset and power OFF l Install an external thermal relay OCR between the inverter and motors to operate several motors a multi pole motor or a dedicated motor with one inverter When configuring an external thermal relay note that the current indicated on the motor rating plate i...

Страница 78: ... Stegne 11 SI 1000 Ljubljana Phone 386 0 1 513 8116 Fax 386 0 1 513 8170 AKHNATON BULGARIA 4 Andrei Ljapchev Blvd PO Box 21 BG 1756 Sofia Phone 359 0 2 817 6000 Fax 359 0 2 97 44 06 1 INEA CR CROATIA Losinjska 4 a HR 10000 Zagreb Phone 385 0 1 36 940 01 02 03 Fax 385 0 1 36 940 03 SIMAP CZ s r o CZECH REPUBLIC Nové sady 988 2 CZ 602 00 Brno Phone 420 777 731 900 HANS FØLSGAARD A S DENMARK Theilgaa...

Отзывы: