118
Operation of
comparator is the same
as its intention.
Inform Minebea about the contents of
failure and situation at site in details.
Contact output chatters.
2
Set value is good.
Confirmation/change for set value should be
made according to the paragraph 7
−
2
−
2.
Confirmation/change for operation of
comparator, comparative target for
comparator should be made according to the
paragraph 7
−
2
−
3 and 7
−
2
−
4.
Apply setting for hysteresis according
to the paragraph 7
−
2
−
5.
NO
YES
YES
NO
NO
YES
Contact output isn’t ON.
NO
YES
Connecting method is good.
YES
NO
Connect securely according to the paragraph
4
−
3
−
3 and 7
−
1
−
2.
Following causes can be considered.
1
Failure in contact by using other than the
rated capacity of contact.
Capacity of contact
:
AC125 V 0.1 A
or DC30 V 0.5 A.
2
Failure in customer’s input circuit.
Confirm the contact output signal by
referring to the paragraph 7
−
18.