Specifications
Description
Data
Transmission rate
9.6 kbit/s
12 Mbit/s, Auto Baudrate detection
Connection mode
ProfiBus network,
connections can be made/released without affecting other
stations
Protocol
PROFIBUS-DP-V0 SLAVE to IEC 61158
-
Mono or multi-master systems are supported.
-
Master and slave devices, max. 126 nodes possible.
-
Watch-Dog Timer
(see Chapter
)
Configuration
GSD file "SART5230.gsd"
Potential isolation
Yes, optocoupler in lines A and B (RS-485)
Bus termination
Via bus terminating resistor switch
(see Chapter
Addressing
Via software
Switch
must be set to position 0!
Cable type
Special ProfiBus color: violet; screened twisted pair cable
Cable impedance
150
Ω
Cable length
The max. distance of 200 m can be extended at 1.5 Mbit/s by
means of an additional repeater.
Certificates
Profibus test center Comdec in Germany and PNO (Profibus
User Organization).
Industry-compatible CE, UL and cUL
4 Device installation
Transmitter in field housing PR 5230
EN-79
Minebea Intec