Sequence of net discharge with filling signals "coarse/fine"
Taring:
The current weight is saved as the tare and
the net weight starts at zero.
Coarse:
A coarse flow (coarse and fine) is batched
until the preset value is reached.
Fine:
A fine flow is batched until the switch-off
point (overshoot) is reached.
Calming:
Wait time during which the overshoot is ef-
fective and scale vibrations may settle.
Tolerance Checking:
The weight is determined and checked
against the tolerance values.
8.3.1.3
Interaction mode
You can choose between the following control/operating modes of the device in
production:
-
[Remote proc. control] via OPC/ModBus and/or fieldbus
-
[VNC] (Virtual Network Computing)
The following table shows how individual modes are locked when production starts.
Starting production
Mode
VNC
Remote control
OPC/ModBus
Remote control
fieldbus
Digital inputs Digital out-
puts
[Remote proc.
control]
[VNC]
8.3.2
Configuring digital inputs and outputs
SPM addresses are assigned to the digital inputs and outputs under the [Configuration
digital IOs] menu item.
Note:
The selected SPM address must be unique within the system.
The SPM addresses for the input and outputs are unchanged after a restart.