7.15.9.1
Defining an action
The possible actions are listed in the following table.
Selection list for actions of the inputs [Input 1/2/3 on/off]
Function
SPM Bit
Description
-no action-
---
no function
set marker 1
X64 = 1
Set marker 1
set marker 2
X65 = 1
Set marker 2
set marker 3
X66 = 1
Set marker 3
select net
X72 = 1
Select net
set zero
X112 = 1
Set zero
set tare
X113 = 1
Set tare
reset tare
X114 = 1
Reset tare
set test
X115 = 1
Activate the analog test
reset test
X116 = 1
Finish the analog test
reset PWF
X117 = 1
Reset power fail
set fixtare
X118 = 1
Set fixtare (use the value in address D31
as a tare value)
get fixtare
X119 = 1
Save gross value as fixtare in address
D31
clr marker 1
X64 = 0
Clear marker 1
clr marker 2
X65 = 0
Clear marker 2
clr marker 3
X66 = 0
Clear marker 3
select gross
X72 = 0
Save the gross weight in address D11
Actions can be selected (bits set) for all digital inputs (see table).
Define the action for the rising edge of Input 1 (in this case: When the input signal
changes from 0 to 1, a tare command is generated).
Accordingly, an action for the falling edge can be determined.
1.
Select the appropriate line using the cursor (here: Input 1 on) and confirm.
Transmitter in field housing PR 5230
7 Commissioning
Minebea Intec
EN-202