12.2.5
Special hints for DeviceNet and EtherNet-IP
With these fieldbus types, the sequence of the bytes (only applicable for words and
individual bytes) is inverted.
With long words, this problem does not arise due to compensation by the firmware.
Sequence of bytes 0
3, e.g. with device type and software version, see table below.
Standard sequence
Sequence for DeviceNet and EtherNet-IP
Byte 0
TYPE MSB
Byte 0
SUBVERSION
Byte 1
TYPE LSB
Byte 1
MAIN VERSION
Byte 2
MAIN VERSION
Byte 2
TYPE LSB
Byte 3
SUBVERSION
Byte3
TYPE MSB
Consequently, the sequence on the PLC side must be changed when using the DeviceNet
and EtherNet–IP field bus types.
12.2.6
Fieldbus register
12.2.6.1
Register 0: I/O status bits (read)
Dynamic status
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
Input 3
Input 2
Input 1
Byte 1
Output 3
Output 2
Output 1
Byte 2
Limit 3
Limit 2
Limit 1
Byte 3
12.2.6.2
Register 1: Scale status (read)
Dynamic status
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
DIM
STND
INZSR
CZERO
BELOW0
OVL
>Max
ADUERR
Byte 1
E9
E6
E1
E3
E7
Byte 2
PowerFail
ActionAc-
tive
CmdError
Byte 3
TareActive CalActive
TestActive
Note:
Byte 0 corresponds to byte 7 in the output area; for weight error, see also the table in
Chapter
Bit
Description
ADUERR
Error of analog conversion/load cell circuit (OR function of the E1,
E3, E7 bits).
Transmitter in field housing PR 5230
12 Fieldbus interface