![Milltronics CompuScale III Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/milltronics/compuscale-iii/compuscale-iii_instruction-manual_1796966054.webp)
COMPUSCALE III / BELT SCALE INTERCONNECTION
MMI-2 APPLICATIONS
COMPUSCALE III / LCPA-08 INTERCONNECTION
(Refer to the LCPA-08 instruction manual for LCPA-08 / Belt Scale Interconnection)
1.
Where a belt scale must be installed in a hazardous area consult Milltronics or your
distributor for wiring instructions.
2.
Where the integrator to load cell belt scale cable exceeds 150m (500 ft):
A) remove jumpers from Compuscale III, TB1 - 9,10 and TB1 - 11,12
B) run an additional shielded conductor to the junction box nearest the load cell(s) from:
» Compuscale III TB1 - 10 to loadcell(s) red
» Compuscale III TB1 - 11 to loadcell(s) black
scale
wiring
scale
wiring
COMPUSCALE III
customer’s MSI
# 1 junction box
(nearest tail
pulley)
customer’s MSI
# 2 junction box
(nearest head
pulley)
COMPUSCALE III
LCPA-08
FIG. 4
PL-367
12 – 4