P10
LOW TOTAL CUTOFF
Defines the minimum belt scale load to be processed for Local Total values and Remote Total contact closures.
Range = 0.0 to 100.0 This eliminates totalizer activity caused by the variable loading effect of an empty running
belt.
With calibration complete, the belt running empty, and the Load displayed, observe the highest display value.
Enter the value as a percent of LOAD (material load from Design Data Sheet or P55 display).
Low Total Cutoff % = Empty Belt Load x 100
Full Load
A value of 0 will permit the Total display to count up or down. Remote Total contact
closures cease while the total counts down. The contact closures will resume
when the Total display regains the amount by which it counted down.
enter:
desired value (0 if certification is required, F = 3.0)
P11
RATE DISPLAY DAMPING
Defines the level of damping to be applied to the Rate display. Range = 1 to 999
This may be used to stabilize a fluctuating rate display without affecting accuracy. Higher values provide more
stabilization. Press "Run" to instantly update the Rate display to the current rate.
enter:
desired value (F = 1)
P12
LOAD DISPLAY DAMPING
Defines the level of damping to be applied to the Load display. Range = 1 to 999
This may be used to stabilize a fluctuating load display without affecting accuracy. Higher values provide more
stabilization. Press "Run" to instantly update the Load display to the current load.
enter:
desired value (F = 1)
P13
SPEED DISPLAY DAMPING
Defines the level of damping to be applied to the Speed display. Range = 1 to 999
This may be used to stabilize a fluctuating Speed display without affecting accuracy. Higher values provide
more stabilization. Press "Run" to instantly update the Speed display to the current speed.
enter:
desired value (F = 1)
P14
RATE OUTPUT DAMPING
Defines the level of damping to be applied to the Rate Output. Range = 1 to 999
This may be used to stabilize a fluctuating Rate Output without affecting accuracy. Higher values provide more
stabilization. Rate Output Damping is disabled if the Rate Output Average (P15) feature is utilized. Press "Run"
to instantly update the Rate Output to the current rate.
enter:
desired value (F = 1)
PL-367