REMOTE COMMUNICATION
This mode provides complete access to all CompuScale III functions via a remote mounted CompuScale III.
To receive communication from the local CompuScale III PORT 1 or PORT 2 connection, SW2-6 of the
remote CompuScale III must be closed.
HOST COMMUNICATION
Host communication permits up to 16 CompuScale III’s (serially connected via PORT 1), to communicate with
a computer or Programmable Logic Controller. Refer to Start Up\Hardware Set Up\Unit I.D. Code.
In this mode, data aquisition and analysis is accomplished by a customer supplied software package.
Refer to Protocol.
SERIAL PRINTER COMMUNICATION
Two modes of serial printer operation are available.
The Port 1 mode (similar to previous Milltronics integrator versions) printout is initiated each time:
» a dry contact is provided across pins 7 and 17 of the printer DP25 connector.
» the Printer Test button is pressed.
The printout contains the: time, date, total, and total engineering units.
The Port 2 mode is compatible with any serial printer.
Close the CompuScale III SW2 contact 7 (SW2-7) and set the Data Transmit Interval (P41), Data Message
(P42), and Serial Printer (P43) parameters as desired. Refer to Parameters.
The printout, containing the Data Message selected, is initiated each time:
» a dry contact is provided across the CompuScale III TB1-35 and COM (e.g. TB1-36)
» the Data Transmit Interval elapses.
95/11/09
PL-367
10 – 2