V6-i VRF 50/60Hz
62
Midea
V6
-i
Series S
er
vice M
anual
Menu mode function:
Table 5-2.3:
Menu mode function
Digital display
content
Menu mode
Remarks
n14
Debug mode 1
All indoor units running in cooling mode
n15
Debug mode 2
If all indoor units in the system are the 2nd generation indoor units, all the indoor units
will run in heating mode. Once there is one or more old indoor unit in the system, all the
indoor units will run in forced cooling mode
n16
Maintenance mode
The system does not check the indoor units’ number.
n24
Reserved
n25
Reserved
n26
Backup run
Only available for outdoor unit with two compressors. If one of the two compressors fails,
the other compressor will keep running for up to 4 days and then stop automatically.
n27
Vacuum mode
It is only used in maintenance process. The digital display displays “R006”, and all solenoid
valves are opened and EXVs are opened to the maximum steps.
n31
History error codes
n32
Cleaning history error codes
n33
Reserved
n34
Factory reset
n41
Power limitation mode 1
100% capacity output
n42
Power limitation mode 2
90% capacity output
n43
Power limitation mode 3
80% capacity output
n44
Power limitation mode 4
70% capacity output
n45
Power limitation mode 5
60% capacity output
n46
Power limitation mode 6
50% capacity output
n47
Power limitation mode 7
40% capacity output
nb1
Fahrenheit degree setting (
o
F)
nb2
Celsius degree setting (
o
C)
nb3
Exit auto power save mode
t
nb4
Enter auto power save mode
nb5
Auto snow-blowing mode 1 (customized)
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
15 minutes and run for 2 minute
nb6
Auto snow-blowing mode 2 (customized)
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
30 minutes and run for 2 minute
nb7
Exit auto snow-blowing mode
nb8
VIP address setting
The digital display will display “IdXX”, “XX” stands for VIP address, use UP / DOWN button
to change the VIP address and press OK button to confirm the specified VIP address.
nF1
Reserved
nF2
Reserved
Содержание MV6-i252WV2GN1-E
Страница 3: ...V5 X VRF 50 60Hz 2 Midea V6 i Series Service Manual...
Страница 33: ...V6 i VRF 50 60Hz 32 Midea V6 i Series Service Manual...
Страница 49: ...V6 i VRF 50 60Hz 48 Midea V6 i Series Service Manual...
Страница 50: ...V6 i VRF 50 60Hz 49 Part 4 Field Settings Part 4 Field Settings 1 Outdoor Unit Field Settings 50...
Страница 69: ...V6 i VRF 50 60Hz 68 Midea V6 i Series Service Manual...