V6-i VRF 50/60Hz
91
P
art
6
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
Procedure
2.11.5
F6
Electronic expansion valve coil
connection on main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Electronic expansion valve coil has
malfunctioned
2
Yes
Replace the sensor
No
Replace outdoor main PCB
Notes:
1.
Electronic expansion valve coil connections are port CN70, CN71 and CN72 on the main PCB (labeled 18, 19 and 20, respectively, in Figure 5-2.1 in Part 5,
2.1 “Ports”).
2.
The normal resistances between EXV coil wiring terminals RED and white / yellow / orange / blue are 40-50Ω. If any of the resistances differ from the value,
the EXV coil has malfunctioned.
Figure 6-2.3: EXV coil wiring terminals