V6-i VRF 50/60Hz
78
Midea
V6
-i
Series S
er
vice M
anual
2.5
E5: Abnormal power supply voltage
Digital display output
2.5.1
Description
2.5.2
Abnormal power supply voltage.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
2.5.3
Trigger condition: Outdoor unit power supply phase voltage < 165V.
Recover condition: Outdoor unit power supply phase voltage is > 180V.
Reset method: Resume automatically.
Possible causes
2.5.4
Outdoor unit power supply voltage is abnormal or a phase is missing.
Loosened wiring within electric control box.
High voltage circuit error.
Main PCB damaged.