V6-i VRF 50/60Hz
47
P
art
3
- Con
tr
ol
7.2
Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is
performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor
heat exchanger temperature, indoor heat exchanger temperature and outdoor unit running time. When the outdoor unit is
running in defrosting, the digital display on outdoor main PCB will display “df”.
Table 3-7.5: Outdoor unit component control during defrosting operation
Component
Wiring
diagram label
8-12HP 14-18HP 20-24HP 26-28HP 30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●
●
●
●
●
Fixed frequency
Inverter compressor B
COMP(B)
●
●
●
DC fan motor A
FANA
●
●
●
●
●
Off
DC fan motor B
FANB
●
●
●
Electronic expansion valve A
EXVA
●
●
●
●
●
Position 480 (steps) or 3000
(steps)
Electronic expansion valve C
EXVC
●
●
●
●
●
Position 480 (steps)
Four-way valve
ST1
●
●
●
●
●
Off
Solenoid valve (oil balance)
SV4
●
●
●
●
●
Normal control
Solenoid valve (fast defrosting)
SV5
●
●
●
●
●
On
Solenoid valve (EXV bypass)
SV6
●
●
●
●
●
On
Solenoid valve (indoor units
bypass)
SV7
●
●
Normal control
Solenoid
valve
(inverter
compressor A vapor injection)
SV8A
●
●
●
●
Off
Solenoid
valve
(inverter
compressor B vapor injection)
SV8B
●
●
Off
Solenoid
valve
(inverter
compressor B pressure balance)
SV9
●
●
●
Open before compressor B
startup
Table 3-7.6: Indoor unit component control during defrosting operation
Component
Unit state
Control functions and states
Fan
Thermo on
Off
Standby
Off
Thermo off Off
Electronic expansion valve
Thermo on
480 (steps)
Standby
480 (steps)
Thermo off 480 (steps)
Содержание MV6-i252WV2GN1-E
Страница 3: ...V5 X VRF 50 60Hz 2 Midea V6 i Series Service Manual...
Страница 33: ...V6 i VRF 50 60Hz 32 Midea V6 i Series Service Manual...
Страница 49: ...V6 i VRF 50 60Hz 48 Midea V6 i Series Service Manual...
Страница 50: ...V6 i VRF 50 60Hz 49 Part 4 Field Settings Part 4 Field Settings 1 Outdoor Unit Field Settings 50...
Страница 69: ...V6 i VRF 50 60Hz 68 Midea V6 i Series Service Manual...