V6-i VRF 50/60Hz
84
Midea
V6
-i
Series S
er
vice M
anual
2.8
xE9: EEPROM mismatch
Digital display output
2.8.1
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description
2.8.2
1E9 indicates a compressor A EEPROM mismatch.
2E9 indicates a compressor B EEPROM mismatch.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
2.8.3
Trigger condition: Compressor drive parameter is mismatch.
Recover condition: Compressor drive parameter is match.
Reset method: Manually restart.
Possible causes
2.8.4
Outdoor unit was powered on immediately after being powered off.
Main PCB damaged.