V6-i VRF 50/60Hz
97
P
art
6
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
L1: DC bus low voltage protection
2.13.7
Note:
1.
The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is lower than 350V, L1
protection will be appeared.
Figure 6-2.6: Inverter module terminals
L1 protection
The power supply is abnormal
Check the power supply
equipment
No output from bridge rectifier
Replace the inverter module
No
No
No
Yes
Yes
Yes
Yes
The DC bus voltage (P, N) is abnormal
1
The reactor performs well
Replace the
reactor
No