V6-i VRF 50/60Hz
112
Midea
V6
-i
Series S
er
vice M
anual
Procedure
2.17.5
P2 / H5
ODU stop valves are closed
Yes
Open the stop valves
No
Insufficient refrigerant caused by
refrigerant leakage
1
Yes
Add refrigerant or inspect the system for
leaks
No
The low pressure side is blocked, caused
by crushed or bent pipe, blocked EXV, or
dirty filter
2
Yes
Inspect the system and fix the error. If the
filter is blocked by ice, the piping should
be cleaned
No
The evaporator heat exchange is poor
5
Yes
Inspect the system and fix the error
No
Replace outdoor main PCB
Notes:
1.
An insufficiency of refrigerant causes compressor discharge temperature to be higher than normal, discharge and suction pressures to be lower than
normal and compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. These issues disappear once sufficient
refrigerant has been charged into the system. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of
Refrigerant System”.
2.
A low pressure side blockage causes compressor discharge temperature to be higher than normal, suction pressure to be lower than normal and
compressor current to be lower than normal, and may cause frosting to occur on the suction pipe. For normal system parameters refer to Table 6-3.4 and
6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”.
3.
In cooling mode check indoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check outdoor heat exchangers, fans and air outlets
for dirt/blockages.
Содержание MV6-i252WV2GN1-E
Страница 3: ...V5 X VRF 50 60Hz 2 Midea V6 i Series Service Manual...
Страница 33: ...V6 i VRF 50 60Hz 32 Midea V6 i Series Service Manual...
Страница 49: ...V6 i VRF 50 60Hz 48 Midea V6 i Series Service Manual...
Страница 50: ...V6 i VRF 50 60Hz 49 Part 4 Field Settings Part 4 Field Settings 1 Outdoor Unit Field Settings 50...
Страница 69: ...V6 i VRF 50 60Hz 68 Midea V6 i Series Service Manual...