![Midea IC SI-A-1205 Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/midea/ic-si-a-1205/ic-si-a-1205_service-manual_1791255051.webp)
51
Safety
Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the
electricity power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
Connect discharge resistance (approx.100
Ω
40W) or soldering iron (plug) b, - terminals of the electrolytic
capacitor on the contrary side of the outdoor PCB.
Note: The picture above is only for reference. The plug of your side may be different.
Main parts check
1. Temperature sensor checking
Disconnect the temperature sensor from PCB, measure the resistance value with a tester.
Содержание IC SI-A-1205
Страница 1: ...IC INVERTER SERIES Service Manual 2012 ICSI A 1205...
Страница 10: ...10 Model W D H W1 A B MOR 09HDN1 QC2 660 265 540 732 458 276 MOR 12HDN1 QC2...
Страница 12: ...12 5 Wiring Diagram 5 1 Indoor Unit MSIC 09HRDN1 QC2 MSIC 12HRDN1 QC2...
Страница 13: ...13 5 2 Outdoor Unit MOR 09HDN1 QC2 MOR 12HDN1 QC2...
Страница 24: ...24 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...