8.4.3.5 Evaporator coil temperature protection
TEstop
T2
Off
Decrease
Hold
Resume
TEdown
TEnorm
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed
between 17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-
only mode according to ΔT (ΔT
=T1-Ts).
ΔT=T1
-Ts
Running mode
ΔT
>
2
℃
Cooling
-3
<ΔT≤
2
℃
Fan-only
ΔT≤
-3
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for
20 minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at auto fan of cooling mode and can’t be changed. The louver
angle is the same as in cooling mode.
8.4.5.2 Compressor running rules