If users switch on AC by remote controller, the compressor will run at the Fmax frequency for
several minutes. Then the compressor running frequency will be controlled as below:
3.5
3.0
2.5
2.0
1.5
1.0
0.5
-0.5
T1-Ts
-1.0
A
B
C
D
E
F
G
H
-1.5
0.0
I
J
While the zones of A,B,C... are corresponding to different compressor running frequency.
Meanwhile, the compressor running frequency is limited by the current.
ISTOPCOOL
I
Icmax
Off
Decrease
Hold
Resume
Icmax-I1COOL
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
While the Icmax is limited by the outdoor ambient temperature as below: