20
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air
conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
6.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve
slightly to purge air from the charge hose for 5 seconds
and then close it quickly.
4). Set the 2-way valve to the close position.
Содержание IC SI-A-1205
Страница 1: ...IC INVERTER SERIES Service Manual 2012 ICSI A 1205...
Страница 10: ...10 Model W D H W1 A B MOR 09HDN1 QC2 660 265 540 732 458 276 MOR 12HDN1 QC2...
Страница 12: ...12 5 Wiring Diagram 5 1 Indoor Unit MSIC 09HRDN1 QC2 MSIC 12HRDN1 QC2...
Страница 13: ...13 5 2 Outdoor Unit MOR 09HDN1 QC2 MOR 12HDN1 QC2...
Страница 24: ...24 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...