6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose
from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the
hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
6.5 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make
the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
Electronic scale
Содержание IC SI-A-1205
Страница 1: ...IC INVERTER SERIES Service Manual 2012 ICSI A 1205...
Страница 10: ...10 Model W D H W1 A B MOR 09HDN1 QC2 660 265 540 732 458 276 MOR 12HDN1 QC2...
Страница 12: ...12 5 Wiring Diagram 5 1 Indoor Unit MSIC 09HRDN1 QC2 MSIC 12HRDN1 QC2...
Страница 13: ...13 5 2 Outdoor Unit MOR 09HDN1 QC2 MOR 12HDN1 QC2...
Страница 24: ...24 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...