32
Auto fan:
2.0
T1-Ts
100%
80%
60%
40%
1%
1.5
1.0
0.5
0.0
-0.5
-1.0
90%
20%
8.4.2.4 Condenser temperature protection
TP4
T3
TP3
Off
Decrease
Hold
Resume
TP2
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
8.4.2.5 Evaporator temperature protection
---T2<0
℃
, the compressor will stop and restart when T2
>=
5
℃
.
---0
℃≦
T2<4
℃
, the compressor frequency will be limited and decreased to the lower level
---4
℃
≤T2≤7
℃
, the compressor will keep the current frequency.
---T2>7
℃
, the compressor frequency will not be limited.
8.4.3 Heating Mode
8.4.3.1 Compressor running rules:
The maximum operation frequency of the compressor after starting submits to the following rule.