Chapter 9 User interfaces
Universal inputs
(PWM mode 1/2)
PWM
(1/2)
Filter time Time in [ms] during which the signal must remain
constant to initiate a level change. Used to suppress
brief faults (debouncing).
Decay
Temporal function in the measurement cycle
off
Decay deactivated
min
The minimum of the last x measurement
values is recorded.
max
The maximum of the last x measurement
values is recorded.
avg
The arithmetic mean of the last x
measurement values is recorded.
med
The median of the last x measurement
values is recorded.
rms
The root mean square of the last x
measurement values is recorded.
Time
Decay period. Up to a maximum of 60 measurement
valuescan be used for the calculation (e.g. 1 channel:
60 measurement values; ... 4 channels:
15 measurement values each). To calculate the number
of measurement values that are taken into account,
refer to "Example to clarify the record interval,
measurement cycle and burst interval in conjunction
with the decay" in chapter "Basic settings" on page
96.
Hold
Hold the last valid measurement value for x
measurement cycles
off
Function deactivated
1-5
Number of measurement cycles for which
the measurement value is held until the
error value is issued
on
In the event of an error, the last valid
measurement value is held until a new
valid measurement value is present.
Rev. 06
73
Содержание myDatalogEASYplus
Страница 2: ......
Страница 8: ...Chapter 18 Contact information 139 8 Rev 06 ...
Страница 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 06 9 ...
Страница 10: ......
Страница 22: ......
Страница 40: ......
Страница 62: ......
Страница 101: ...Chapter 9 User interfaces 9 2 2 4 GPRS SIM tariff Selected SIM tariff Rev 06 101 ...
Страница 102: ......
Страница 110: ......
Страница 112: ......
Страница 118: ......
Страница 120: ......
Страница 136: ......
Страница 138: ......