MHS Boilers Ltd ©
191007
27
• Type C83:
Room Sealed appliances in cascade, connected to separate air supplies but common flue discharge
through the roof.
5.3.4.2 Air inlet pipe
The air supply pipe may be single wall, smooth or flexible, and be made of:
• plastic
• aluminium
• stainless steel
Always consider the large resistance when using flexible material.
Always consider condensate formation due to the suction of cold air.
Type
Diameter of air inlet D1 (mm)
WM/45 80
WM/65 80
WM/85
100
WM/100
100
WM/120
100
Table 3 Diameter of air inlet
The connection for the air supply is on the top of the boiler.
The air supply pipe should be airtight. This is to prevent the suction of ‘false air’. Horizontal
components in the air supply should be installed sloping in the direction of the supply opening.(Fresh
air opening)
5.3.4.3 Flue gas outlet
The flue gas components may be single wall, smooth, Rigid or flexible, and be made of:
• plastic
• stainless steel
Always consider the resistance when using flexible material.
Type
Diameter of Flue Gas D (mm)
WM/45 80
WM/65 80
WM/85
100
WM/100
100
WM/120
100
Table 4 Diameter of flue gas outlet
The flue gas outlet is located on the top of the appliance and is designed for direct connection to a
corrosion resistant flue pipe.