KKM8
This is a boiler cascade manager with which up to 8 boilers can be connected in cascade and an
extra on/off boiler can be operated. The KKM8 also has the same functional features as the E8.1121.
Controller Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation (230 Volt Terminals)
Block Terminal #s
Voltage
Screened Cable
(Earthed Screening)
Description/Operation/Function
II
1
230V
-
Permanent Neutral
II
2 & 3
230V
-
Permanent Live
II
4 (A1)
230V
-
Heating Zone 1 Pump 230V Output (Max 1 Amp)
II
5 (A2)
230V
-
Heating Zone 2 Pump 230V Output (Max 1 Amp)
II
6 (A3)
230V
-
Hot water Charging Pump 230V Output (Max 1 Amp)
II
7 (A4)
230V
-
Heating Zone 2 Mixing Valve 230V ‘Open’ Output (Max 0.5
Amp)
II
8 (A5)
230V
-
Heating Zone 2 Mixing Valve 230V ‘Close’ Output (Max 0.5
Amp)
II
9 & 10
230V
-
Do Not Use (Volt Free Stage One Burner Enable)
VI
1 & 2
230V
-
Do Not Use (Volt Free Stage Two Burner Enable)
IV
1 (A8)
230V
-
Heating Zone 1 Mixing Valve 230V ‘Open’ Output (Max 0.5
Amp)
(Multifunctional Relay 1 Output)
IV
2 (A9)
230V
-
Heating Zone 1 Mixing Valve 230V ‘Close’ Output (Max 0.5
Amp)
(Multifunctional Relay 2 Output)