Lamp feeder cable: approved types and lengths
The use of cable types which have not been approved by the manufacturer
can lead to malfunction. The possibility of damage to the electronic ballast
cannot be excluded.
Typ
ELC X24-210
ELC X24i-210
ELC X24B-210
Artikel-Nr. 8045*
U
0
/U = 1.8/3kV
2x4mm²
Ø 16.9mm
GL-approved
on request
on request
on request
The data refers to the distance between ELC and lamp.
* This cable cannot be connected directly to the ELC due to the diameter.
Mechanical characteristics
Type
ELC X24-210
ELC X24i-210
ELC X24B-210
Dimensions
(approx. H x W x D)
250 x 470 x 420 mm
Weight (approx.)
41 kg
Installation position
horizontal as described in 3.1
Control characteristics
Type
ELC X24-210
ELC X24i-210
ELC X24B-210
Current requirement of 24V-
supply (X805.5)
4.4A max. for ELC
control circuitry
Output currents of
X806 Pins 5 + 6 have
to be added
4.9A max. for ELC
control circuitry
Output currents of
X806 Pins 5 + 6 have
to be added
4.4A max. for ELC
control circuitry
Output currents of
X806 Pins 5 + 6 have
to be added
Baud rate
PROFIBUS: 500kBit
MODBUS: Baud rate 19200, 8 Databits, Even parity, 1 Start/Stop Bit
☞