5
Monitoring, warning, error, repair
page 43
ELC X-Series-V1.3-09.16-GB
subject to technical alterations
5.4.3 Resetting the error register
Each error has to be acknowledged by setting the
{Clear Error}
bit in register
[Lamp Control]
to “1”. First of all set the
{Start Lamp}
bit
in register
[Lamp Control]
to 0. Then only the
transgression of the
{Clear Error}
bit from “0” to “1” can reset the
[Error Register]
. After the
PROFIBUS has transmitted the [Lamp Control] Register (check e.g. via the [Error Register]:
if error eliminated all error bits are „0“ again) and after an ELC internal synchronisation time of
additional 15 ms, the
{Clear Error}
-bit has to be reset to „0“.
PROFIBUS-output data (Master
→
ELC)
Byte-
Nr.
0
1
2
3
4
5
Name
[Power
Set
Value]
[Installed
Lamp
Power]
[Lamp
Control]
[Reserved]
↓
Bit
7
6
5
4
3
2
1
0
Name
n/a n/a n/a n/a n/a n/a
Clear
Error
Start
Lamp
5.5 Repair ELC
Only the manufacturer is permitted to repair the ELC. In case of failure please contact the
following address: