Appendix - "Bus analysis" mode
126
12.8.3. Measurements (FlexRay)
UBus = U_BP – U_BM
Diagnosis
Use this table to troubleshoot problems on a measurement :
Measurement
Description
Diagnosis
UBus High
Measurement of the high level on the
Ubus signal
Termination problem
Junction connection (oxidation, bad
contact, …)
Cable length not compliant with standard
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
UBus Low
Measurement of the low level on the
UBus signal
Time Data
Measurement made using the bit time
total.
Unsuitable or damaged cable
Termination impedance incorrectly positioned
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
TRise
Rise time between 20% and 80% of
the UBus signal amplitude
Unsuitable or damaged cable (the rise and fall
times increase with the cable impedance)
Termination impedance incorrectly positioned
…
TFall
Fall time between 80% and 20% of
the UBus signal amplitude
UCm
Offset measurement on the U_BP
signal
Chassis-ground disturbance problem
Common mode problem
Cable length not compliant with standard
…