MI 3394 CE
MultiTester
XA
Single tests
89
6.2.6
HV DC programmable
IMPORTANT SAFETY NOTE
Refer to chapter
for more information regarding safe use of the
instrument.
In the HV DC programmable test the time dependency of high voltage can be set according to
diagram on
Figure 6.33: HV DC programmable test menu
Test results / sub-results
U............... measured test voltage
I ................ test current
Ic .............. capacitive portion of test current
Ir ............... resistive portion of test current
Test parameters
Starting DC test voltage
U start [500 V ... 6000 V in steps of 50 V]
DC test voltage
U test [500 V ... 6000 V in steps of 50 V]
Duration of starting voltage
t start [1 s ... 120 s ]
Duration of ramp
t ramp [2 s ... 60 s ]
Duration of test voltage
t end [Off, 1 s ... 120 s ]
Test limits
High limit (I)
H limit [Custom, 0.05 mA ... 10.0 mA ]
Low limit (I)
L limit [Off, Custom, 0.05 mA ... 10.0 mA]