Do not drain water from the central heating system during standstill. Unless it is required for repair
or assembly work. In order to prolong the life of the boiler it is recommended to leave the boiler in
an open position for the time of standstill, enabling free air flow through its interior, and
consequently drying.
NOTE!
Due to the specificity of the boiler operation, under normal conditions of its operation in
accordance with the manual and protection in the open system according to PN-91/B-2413,
in case of lack of electricity the boiler is automatically extinguished and does not pose any
danger.
7. identification of disturbances in the correct operation of the boiler
L.p.
Symptom
Cause
Method of disposal
1.
Return of fire to the fuel tank
▪
no or too low fuel level in the
tank
▪
fuel hanging
●
unsealed tray lid
●
refuel in the tank
●
mix
●
check the tightness of the lid
▪
locked piston system
●
power outage for a long time
●
no water in the water system
for the 'firefighter' system
●
go through the shutdown
and extinguish the boiler
●
select fuel from the tank and
fill it with water
●
abnormal chimney draught
●
unclosed boiler door (picture
13)
●
install a chimney draught
regulator, improve draught
●
close the stove door
2.
Suspension of fuel in the tank
●
use of fuel with a dust
content of more than 5%,
e.g. sawdust
●
too moist fuel (over 30%)
that freezes to the walls in
winter
●
fuel transition
●
add a portion of dry fuel and
mix thoroughly
3.
Fume evacuation into the fuel
tank
●
contamination of the
combustion chamber
●
unobstructed chimney
●
boiler door and covers not
closed
●
no air supply to the boiler
room
●
go through the shutdown
and extinguish the boiler
●
clean the ash chamber
●
clear the chimney
●
install a draught excluder
●
shut the gusts and doors in
the boiler
●
check the boiler room
ventilation
4.
Rapid build-up of carbon
deposits in the furnace head
●
over-polluted fuel
●
wrong fuel
●
use fuel in accordance with
the instructions
●
remove the decoction
5.
Fuel feeder blocking
●
using the wrong fuel
fraction, significantly above
the manufacturer's
recommendations
●
perform an emergency
shutdown of the boiler
●
empty the fuel tank
●
cause of the jam
6.
Locking of the feed flap
●
using the wrong fraction of
fuel
●
fall of the spring securing
the return of the feed flap
(fig. 1)
●
perform an emergency
stopping procedure for the
boiler
●
check the correct installation
of the feeding flap spring