MC³ 24.96.EX O&M Manual
Page 64
08/14/01 4:34 PM/LDD
Parameter
Quick Setup value
Belt length decimal points
Three
Feedrate decimal points
To produce five significant digits in the display
Speed decimal points
To produce four significant digits in the display
Totalizer cutoff
Negative 10% of design load
Scaler for analog input 1
Design Feedrate
Low Feedrate
10% of design feedrate
High Feedrate
90% of design feedrate
Low and high absolute
setpoint deviation
10% of design feedrate
Overload Limit
Design load
Underload Limit
Negative 10% of design load
High Speed
Design speed
Nominal speed (no tacho)
Design speed
Max Zero Track Load
10% of design load
Max Zero Track Step
1% of design load
Max Zero Track
4% of design load
SOLVING PROBLEMS
If the following procedures do not assist in solving your problem, see Technical Support on page 2
on obtaining factory support for your controller.
Unit does not power up
WARNING:
Only Qualified service technicians should work on the controller. When working with live voltages
insure all safety precautions are taken..
1. Check wiring harnesses, Power running to the controller
2. Verify that the fuses are good. There are two fuses in the controller. One is in the power
receptacle and the other is on the power supply board.
3. Using a volt meter, verify that 110V is present at the power supply
4. Verify that the +5 volt and ±12 volts at the power supply are good.
Controller Fails to Boot Up
1. If the message “Bad Register Checksum, Press OK to Continue” appears during boot-up, hit
OK and the controller should continue to initialize. After the controller has initialized, check all
settings carefully before operating the Feeder.
2. By pressing the upper left and right corners of the touch screen simultaneously during
initialization, a screen will be displayed that will ask if you would like to reset the registers to
reasonable values. This will set the feeder to the factory defaults, which will be different from
your actual setup. You must re-enter all of your operating parameters and re-calibrate the
feeder before normal operation can resume.
WARNING:
Make sure that you check all settings carefully before starting the feeder. Otherwise the feeder
could operate in an unsafe mode.