MC³ 90.10.EX O&M Manual
- 30 -
inputs. For example the Physical Input "Rack 2 Input 1" may be mapped to the Logical Inputs
"Calibr. Access" and "Advanced Set". This will allow calibration acceptance and custom setup
access only if the input Rack 2 Input 1 is set appropriately.
Digital input screens
List of Logical Inputs
Name
Description
Feeder Block
This input is used to unconditionally stop the feeder.
Run Permission
This input is used to start and stop the all feeders associated with
the selected recipe. The feeders will start when this input is on.
The Start and Stop Feeders buttons will be enabled and can be
used to start and stop all feeders. .
Frc Comm Setpt
Force the controller to use the Serial feedrate setpoint when the
controller is in communications with a serial device.
Reset Faults
Used to externally reset FAULTS.
Reset Warnings
Used to externally reset WARNINGS.
Sends the selected print string to the printer serial port.
EMT Enabled
When off, the pulses going to External Electromechanical
Totalizer (EMT) are disabled.
Total Enabled
Enables the main Totalizer. When Off, the main total does not
increment.
Sub-Total Enabl
Enables Sub Totalizer. When Off, the sub total does not
increment.
Extended Access
Allows access to calibration constants in the register editor and
via communications.
Register Access
Input permitting the user to access to the Register Editor (page
37).
Lck Setpnt Mode
Locks Setpoint method to the current one selected. The buttons
that change the setpoint method will disappear from the screen.
Limit Setpoint
Switch used to clamp the feedrate setpoint between the limits set
in the (page 43) section of the Limit Switches menu.
Start Feeders
Input to start feeders remotely. Can only be used when Run
Permission is enabled.
Stop Feeders
Input to stop feeders remotely. Can only be used when Run
Permission is enabled.
Available I/O 1/8
I/O points that may be used by an external communication
device for control.
List of Physical Inputs
Physical Inputs
Description
Always Off
The contact is always equal to 0 (open).
Always On
The contact is always equal to 1 (closed).