MC³ 90.10.EX O&M Manual
- 9 -
Running & Controls
Initial Setup
1. Slaves must be set to use Modbus/RTU. This usually is accomplished by setting the Comm
Protocol Value to 2 then cycling power to use the protocol. Default Line Parameters - Baud
Rate 9600, 8 Data Bits, 1 Stop Bit, Even Parity.
2. One digital input in the slave must be properly configured.
Input
Setting
External Input 1
Run Permission
3. Five digital outputs must be mapped in the slave.
Output
Setting
External Output 1
Fault
External Output 2
Warning
External Output 3
Ready
External Output 4
Running
External Output 5
Good Feedrate
4. The total number of recipes used must be entered into the design parameters.
5. The total number of feeders (slaves) must be entered into the design parameters.
6. There are several parameters from the feeders (slaves) that need to be entered into the MC³
90.10.EX.
Parameter
Port # that the slave feeder is attached to
Controller number for the slave feeder
Type of feeder (Belt feeder, Loss-In-Weight
Feeder, Flowmeter)
Unit settings for each feeder.
Design Feedrate
Design Weight/Load
Design Speed (if not used use default of 100%)
Main Display
The main screen displays the following parameters:
The current selected recipe
The current feedrate of all feeders that are a part of the current recipe
The current setpoint (The method, ex. Local, is displayed within an indicator box.)
The total of the current selected recipe
A Sub-Total of all recipes