TS790+ & TS900+ Installation Manual
Engineer’s Menu 1
33
28 Abort Delay
This timer sets the period in which the alarm
signal may be aborted following an alarm
condition. When an alarm occurs, the “Abort
Output” (071) is only activated if the system is
unset within this period. If the system is unset
after this period the abort output is NOT
activated. This timer has a working range of
000-199 seconds.
System Timers Flowchart
Setting Modes
[1.6]
The setting mode for full set and each part set
can be configured to the following setting
modes:
1 Final
Exit
The system will set when the “Final Exit” circuit
is activated and after the “Settle Time” has
expired.
2 Exit
Terminator
The system will set when the “Final Exit” circuit
is activated, the “Exit Terminator” button is
pressed and after the “Settle Time” has
expired.
3 Timed
Exit
The system will set when the “Exit Time” has
expired or if the “Exit terminator” button is
pressed.
4 Instant
The system will set instantly.
5 Deferred
Any circuit triggered during the exit will restart
the exit timer.
6 Lock
Set
To use this method you must install a lock
switch with the contacts connected to a
lockset zone type.
To set the system the user first enters their
access code at a keypad or operates a
keyswitch. The control unit starts the exit tone.
Note that the exit time is infinite in this option.
The user then operates the final exit zone
and turns the key in the lock switch to
“locked”. The system sets seven seconds
after the lock switch contacts open.
To unset the system the user turns the lock
switch to “unlocked” (closing the lock switch
contacts). The keypads start a continuous
tone. At this point the user can lock the
lockswitch again without causing any alarm.
When the user opens the final exit zone the
control unit starts the entry timer. The user
completes entry by unsetting the system in
the normal way.
Note that when the user unlocks the
lockswitch the control unit disables Alarm
Confirmation. The control unit enables Alarm
Confirmation again if the user locks the
lockswitch without starting the entry timer.
If an intruder opens the final exit door without
first unlocking the lockswitch then the control
unit immediately starts an unconfirmed
alarm. If the intruder goes on to violate
another zone and you have enabled Alarm
Confirmation then the control unit sends a
confirmed alarm.
Содержание TS790+
Страница 1: ...TS790 TS900 Intruder Alarm Control Panels Installation and Programming Manual...
Страница 11: ...TS790 TS900 Installation Manual System Installation 7 Control Panel PCB Layout Figure 6 TS790 TS900 Main PCB...
Страница 57: ...TS790 TS900 Installation Manual Engineer s Menu 3 53 Program Digi Flowchart...
Страница 63: ...TS790 TS900 Installation Manual Appendices 59 Figure 27 Commercial Premises...