![Menvier Security TS790+ Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/menvier-security/ts790/ts790_installation-and-programming-manual_1771195026.webp)
System Installation
TS790+ & TS900+ Installation Manual
22
Power-Up Checks
When the initial power-up checks have been
completed, check the following:
1. Switch off the 240V mains supply and
measure the DC voltage at each Node and
remote keypad and ensure the voltage is
greater than 12.8V whilst the system is
powered from its standby battery.
2. Switch on the 240V mains supply and
measure the DC voltage between the mains
earth connection and AUX +12V. Then
measure the DC voltage between the mains
earth connection and AUX 0V. In both cases
the measurement should be 1V or less. If the
voltage is greater than 1V, the system has
an “Earth Fault” and all cables should be
checked for isolation to Earth.
3. Using a voltmeter measure the DC voltage
across the control panel PCB test points (V)
and calculate the system current
consumption (see page 8). Ensure that the
reading is not greater than 1.5A.
4. Repeat test (3) with the system in an alarm
condition and ensure that the reading is not
greater than 1.5A.
¨
The TS790+ & TS900+ have an
overload protection circuit. If the power
supply is overloaded, the display will
show: “PSU OVERLOAD ! ! !” and sounder
will sound.
NVM Defaults
Section Option
Default
User 00 Engineer
1234
User 01 Master
5678
User
Codes
User 02 - 31
Not Used
Panel Output 1
Walk Test (004)
Panel Output 2
Courtesy Light (012)
Panel Output 3
Switch 12V (002)
Panel Output 4
Detector Reset (003)
Panel Output 5 KP1
Code Accepted (009)
Panel Output 6 KP1
Code Accepted (009)
Panel Output 7 KP2
Code Accepted (009)
Panel
Outputs
Panel Output 8 KP2
Code Accepted (009)
Digicom Output 1
Fire (007)
Digicom Output 2
PA (006)
Digicom Output 3
Alarm (005)
Digicom Output 4
System Set (008)
Digicom Output 5
Active Omit (080)
Digicom Output 6
Bell (000)
Digicom Output 7
Confirmed Alarm (011)
Digicom
Outputs
Digicom Output 8
(not on JP9/10)
Tamper Fault (020)
Digi Channel 1
Fire (007)
Digi Channel 2
PA (006)
Digi Channel 3
Alarm (005)
Digi Channel 4
System Set (008)
Digi Channel 5
Active Omit (080)
Digi Channel 6
Bell (000)
Digi Channel 7
Confirmed Alarm (011)
Digi
Channels
Digi Channel 8
Tamper Fault (020)
XNode Output 1
Walk Test (004)
XNode Output 2
Courtesy Light (012)
XNode Output 3
Switch 12V (002)
XNode Output 4
Detector Reset (003)
XNode Output 5
Code Accepted (009)
XNode Output 6
Code Accepted (009)
XNode Output 7
Code Accepted (009)
XNode Output 8
Code Accepted (009)
XNode Output 9
Code Accepted (009)
XNode
Outputs
XNode Output 10
Code Accepted (009)
Circuit 01
Final Exit
Circuit 02
Night (Access)
Circuit 03 - 06
Night
Circuit 07
Exit Terminator
Circuit 08
PA Audible
Circuit 09 (Kpd 1)
Final Exit
Circuit 10 (Kpd 1)
PA Audible
Circuits
Circuit 11 - 56
Not Used
00 Test Call At
000 hours
01 No of Re-arms
000
02 Settle Time
007 seconds
03 Part Set Coms Dly 000 seconds
04 Exit Time
030 seconds
05 Entry Time
015 seconds
06 Bell Duration
020 minutes
07 Bell Delay
000 minutes
08 D-Knock Delay
008 seconds
09 Test Time
014 days
System
Timers
10 Second Entry
000 seconds
Содержание TS790+
Страница 1: ...TS790 TS900 Intruder Alarm Control Panels Installation and Programming Manual...
Страница 11: ...TS790 TS900 Installation Manual System Installation 7 Control Panel PCB Layout Figure 6 TS790 TS900 Main PCB...
Страница 57: ...TS790 TS900 Installation Manual Engineer s Menu 3 53 Program Digi Flowchart...
Страница 63: ...TS790 TS900 Installation Manual Appendices 59 Figure 27 Commercial Premises...