Engineer’s Menu 1
TS790+ & TS900+ Installation Manual
32
when the user enters their passcode the exit
timer starts and the system attempts to set,
on entering their passcode during entry, the
wards assigned to their “Code Set Group”
are unset. If the timer is set to anything other
than zero all “Code Set Group” users are
displayed a “Ward Selection Menu”. The
menu will prompt the user to select the
wards that they require to set and unset
during the setting & unsetting procedure.
The user can only select the wards which
have been allocated to their “Code Set
Group”, e.g., If “Code Set Group A” has
been defined by the engineer to set wards B
& C, the user can only affect wards B & C.
Note: standard and master users may also
access the “Ward Selection Menus”, see
timer 21. This timer has a working range of
000-199 seconds.
19 Test Call
If the system is fitted with a plug-on digicom
(DC3, DC3M, DC54, DC58 or DC58M) it is
possible for the control panel to make the
digicom send a timed test call to the central
station. The “Test Call” timer sets the period
of activation, i.e., 000=Disabled, 001=daily,
007=weekly etc. Once programmed the
digicom will send the test call at 3.00 AM.
This timer has a working range of 000-199
days.
20 Confirmation Time
This timer controls the duration of the “Alarm
Confirmation” period. The timer has a
working range of 000-199 minutes.
21 Part Set Codes
The value of this counter determines which
standard users are given access to the
“Ward Selection Menu”. For example if the
counter is set to 021, users 21 through to 31
have access to the menu. If the timer is set
to 032 or above, none of the
standard/master users have access to the
menu. This counter has a working range of
000-199. Note: “Code set Groups” are not
affected.
22 Line Fault Delay
This timer delays the “audible” line fault
indication when a telephone line fault
occurs. The display and any outputs
programmed as “Line Fault” are not
affected. This timer has a working range of
000-198 minutes. If you set the timer to 199
then the control unit stops the audible fault
indication (but still logs the fault and shows it
on the display).
23 Mains Off Delay
This timer delays the “audible” mains off
indication when the mains power is
removed. The display and any outputs
programmed as “Mains Off” are not
affected. This timer has a working range of
000-198 minutes. If you set the timer to 199
then the control unit stops the audible fault
indication (but still logs the fault and shows it
on the display).
24 No Remote Resets
This counter determines how many coded
“Remote Resets” can occur before the
system locks into engineer reset only. Note:
Remote Reset by the RR pins are also
affected by this counter. This counter has a
working range of 000-199.
25 Monitor Duration
This timer affects the duration of the “Timed
Output” (No. 070). This timer has a working
range of 000-199 minutes.
26 Activity Duration
This timer sets the duration for which all
“Flagged” circuits must be activated within in
order that the system may be set without
flagging inactive circuits. Once the timer
expires it is restarted and all “Flagged’
circuits must once again be re-activated.
This timer has a working range of 000-199
hours.
27 Part Set Entry Time
This timer sets the entry period for the system
when the system is in the part-set condition.
If the timer is set to 000 the part-set entry
timer is the same as the main entry timer
(timer 05). This timer has a working range of
000-199 seconds.
Содержание TS790+
Страница 1: ...TS790 TS900 Intruder Alarm Control Panels Installation and Programming Manual...
Страница 11: ...TS790 TS900 Installation Manual System Installation 7 Control Panel PCB Layout Figure 6 TS790 TS900 Main PCB...
Страница 57: ...TS790 TS900 Installation Manual Engineer s Menu 3 53 Program Digi Flowchart...
Страница 63: ...TS790 TS900 Installation Manual Appendices 59 Figure 27 Commercial Premises...