TS790+ & TS900+ Installation Manual
Engineer’s Menu 1
31
activated and the “2nd Entry. . .” timer is
started. This timer has a working range of
000-199 seconds.
06 Bell Duration
This controls the duration of the external
bell/sounder. If the timer is set to 199 the bell
output is continuous. This timer has a working
range of 000-199 minutes.
07 Bell Delay
This timer delays the activation of the
external bell/sounder and internal sounders.
This timer has a working range of 000-199
minutes. Note: Any alarm during the entry
procedure will cancel the bell delay.
08 Double Knock Delay
This is the “Double Knock” time window in
which either two circuit activation must
occur within this time to generate an alarm
condition. Or the circuit must remain active
for the whole duration of this time to
generate an alarm condition. This will only
apply to circuits with the “Double Knock”
attribute. This timer has a working range of
000-199 seconds.
09 Test Time
This timer varies the number of days that
“Test” attribute may be applied to a circuit. If
the timer is set to 000 then circuits will remain
on test until the “Test” attribute is removed.
This timer has a working range of 000-030
days.
10 Second Entry
When the “Entry Timer” has expired the “2nd
Entry timer” starts to count down, if at the
end of this time the system or area has not
been unset then a full alarm will be
generated. This timer has a working range of
000-199 seconds.
11 Service Time
The installation company may use this timer
to periodically generate a “SERVICE
REQUIRED” message so that the user is
reminded that a service call is required. The
users may continue to set and unset the
system. When the engineer attends the site
and enters their passcode the message is
cleared. The service timer is re-started when
the engineer re-selects this timer option. To
disable this feature set the timer to 000. This
timer has a working range of 000-199 weeks.
12 Payment Time
The installation company may use this timer
to prevent the users from setting the system.
When the timer has expired the “CALL
ENGINEER” message is displayed and the
users are unable to set the system until the
engineer has reset the system or the user
has been provided with a “Remote Reset”
code. To disable this feature set the timer to
000. This timer has a working range of 000-
199 weeks.
13 Part Set Bell Delay
This timer delays the activation of the
external bell/sounder and internal sounders
when the system is part set. This timer has a
working range of 000-199 minutes. Note:
Any alarm during the entry procedure will
cancel the bell delay.
14 Courtesy Duration
This timer is used to control the duration of
the output type “Courtesy Light”. This timer
has a working range of 000-199 seconds.
15 Access Code Duration
This timer is used to control the duration of
the output type “Access”. This timer has a
working range of 000-199 seconds.
16 Modem Rings
This counter is for use with the DC58M, it
allows the installer to specify how many rings
are required before the DC58M picks up the
call. If the counter is set to 000 it will pick the
call up as soon as any incoming ringing is
detected. Note: If the system is fitted with a
DC3M, the counter must be set to zero. This
counter has a working range of 000-199.
17 Contact ID Alarms
When using the DC58 or DC58M and
"Contact ID Extended Reporting". The
number of Contact ID alarms that are
transmitted to the central station per circuit
are controlled by the value of this counter.
e.g., if the counter is set to 003 then all
circuits will report 3 activation’s before they
are locked out from sending any more.
Note: this does not affect the re-arm of the
zone. This counter has a working range of
000 - 199.
18 Ward Menu Duration
If the timer is set to 000 the “Code Set
Group” passcodes function as normal, i.e.,
Содержание TS790+
Страница 1: ...TS790 TS900 Intruder Alarm Control Panels Installation and Programming Manual...
Страница 11: ...TS790 TS900 Installation Manual System Installation 7 Control Panel PCB Layout Figure 6 TS790 TS900 Main PCB...
Страница 57: ...TS790 TS900 Installation Manual Engineer s Menu 3 53 Program Digi Flowchart...
Страница 63: ...TS790 TS900 Installation Manual Appendices 59 Figure 27 Commercial Premises...