Technician Settings (Cont’)
P31 – Fan ON delay in cooling (FC Only!)
Range: 0…120
seconds
Default: 0 seconds (no delay)
P32 – Fan OFF delay in cooling
Range: 0…120
seconds
Default: 0 seconds (no delay)
P33 – Fan ON delay in heating (FC Only!)
Range: 0…120
seconds
Default: 0 seconds (no delay)
P34 – Fan OFF delay in heating
Range: 0…120
seconds
Default: 30
seconds
Fan ON delay
in cooling
(seconds)
Fan OFF delay
in cooling
(seconds)
Fan ON delay
in heating
(seconds)
Fan OFF delay
in heating
(seconds)
ON
OFF
Fan OFF
delay
Fan ON
delay
Time
(sec.)
Valve
Fan
P31 – P34
Fan on/off delay
with fan on demand
(auto fan) active.