Technician Settings (Cont’)
P101 – Screen dimming delay
Range: 0...99 minutes
Default: 5 minutes
P107 – Weekly program configuration
“00” - Disable weekly program (program parameters will be lost)
“01” - 7 days with the same program
“02” - One program for Monday to Friday
and another program for Saturday and Sunday
“03” - One program for Monday to Friday,
one for Saturday and another for Sunday
“04” - 7 days with the different program for each day
P108 – Weekly program - events per day
“00” - Two different events per day
“01” - Four different events per day
P109 – Weekly program event configuration
“00” - US Program
Event start time, Mode, Fan speed, Set points (one or two)
“01” - Eu program
Event start time, Stop time
Screen dimming
delay
Weekly program
configuration
Weekly program
events per day
Weekly program
event configuration
- 55 -
P111 – PIR Sensitivity
Range: 1...5 (1 – Less sensitive, 5 – More sensitive)
Default: 4
PIR Sensitivity