Technician Settings (Cont’)
P36 – Freeze protection cut-in set point
Range: 8...15°C
/
46…59°F
Default:
8°C / 46°F
P37 – Freeze protection cut-out set point
Range: 10...17°C
/
50…63°F
Default: 10°C
/
50°F
Freeze protection cut-in set point
Disable freeze
protection
Enable freeze
protection
P35 – Enable/Disable Freeze protection
“00” - Disable Freeze protection
“01” - Enable Freeze protection
(°F)
(°C)
Freeze protection cut-out set point
(°F)
(°C)
Note: If enabled, freeze protection will start when the
thermostat is either ON or OFF and regardless of the
current system mode.
The room ambient temperature which will trigger
Heating ON.
The room ambient temperature which will switch the
Heating back OFF.