Operating instructions

Turning the thermostat ON and OFF

Press the [On/Off] button to turn the thermostat ON or OFF.

Selecting temperature scale

In One set point configuration:

Press the [+] or [-] buttons once to view the set point temperature. 
Use the [+] or [-] buttons to adjust the set point.

In Two set points configuration:

Press the [+] or [-] buttons once – “    ” and the set point temperature for 
cooling will appear on display. 
Use the [+] or [-] buttons to adjust the set point for cooling.
Press the [Mode] button or wait 3 seconds – “    ” and the set point 
temperature for heating will appear on display.
Use the [+] or [-] buttons to adjust the set point for heating.

Notes: 
- The set point for cooling must be higher than the set point for heating. 
- For humidity set-point please refer to technician settings – parameter P197.

OFF

ON

Celsius

Fahrenheit

Adjusting the Set point temperature

Press the [C/F] button to switch between temperature scales.

Set point

Set point

For heating

Set point

For cooling

- 5  -

Содержание ETNC-SUPER-PROG-HU-PIR

Страница 1: ...ETNC SUPER PROG HU PIR Owner s manual Technician Settings Rev 1 5 a Mode Fan C F Prog On Off ...

Страница 2: ...g P04 Lock the Fan button P05 Lock the Mode button P06 Lock the On Off button P07 Lock the and buttons Set buttons P08 Functionality of T1 terminals P09 Functionality of IN1 0 terminals P10 Window contact terminals IN1 0 polarity P11 Window contact delay time P12 Door switch terminals T1 0 polarity P13 Door switch delay time P14 Enable Disable Auto change over mode P15 Occupancy sensor logic PIR P...

Страница 3: ... limit in cooling P78 Fan VFS Low limit in heating P79 Fan VFS High limit in heating P83 View T2 temperature sensor readings P84 View T3 temperature sensor readings P85 Deice in cool cut in temperature P86 Deice in cool cut out temperature P87 Deice in heat time P88 Deice in heat break time P89 Deice in heat cut in temperature P90 Deice in heat cut out temperature P91 Compressor delay P98 Display ...

Страница 4: ...lect Fan speed Low Medium High Auto Press and hold to activate fan on demand Press to select System Mode Cool Heat Auto Press to turn unit On or Off Ambient Set point indication temperature Ambient humidity indication Thermostat On Off indication System MODE indication Clock Weekdays Fan only Cooling Heating Auto mode Press to switch between temperature scales ºC ºF Press and hold to enter weekly ...

Страница 5: ...oling will appear on display Use the or buttons to adjust the set point for cooling Press the Mode button or wait 3 seconds and the set point temperature for heating will appear on display Use the or buttons to adjust the set point for heating Notes The set point for cooling must be higher than the set point for heating For humidity set point please refer to technician settings parameter P197 OFF ...

Страница 6: ...play 2 Medium speed available in 3 speeds configuration Selecting Fan speeds for 2 and 3 fan speeds configuration Low Medium High Auto Press the Mode button to switch between system modes Notes 1 During demand for cooling or heating the active mode will flash 2 In Auto mode the active mode icon Cool or Heat will flash 3 Auto mode is not available in 2 Pipe system configuration Selecting system mod...

Страница 7: ...perating instructions Cont Temperature Time Normal work Freeze protection Cut in Cut out Economy mode Economy mode can be activated by triggering a Window contact Remote on off switch Window contact remote economy switch door switch key tag the built in external PIR sensor passive infrared sensor or through communication binary value UnoccupiedByNetwork When Economy mode is active the thermostat w...

Страница 8: ...y like External sensor Soft start in heat sensor Deicing in cool Door switch Key tag Whenever there is demand for cooling and the outdoor temperature conditions allow the operation of the economizer it will operate together with the regular cooling system and will not replace it Economizer will start and run as long as both of the following conditions are satisfied Teconomizer temperature Room tem...

Страница 9: ... and fan speed Weekly program 9 Important Parameter P107 must not be equal to 0 in order to enable weekly program capabilities Changing P107 to 0 will disable all program capabilities and reset programmed information Activate Temporarily disable Override the program Activate the program When the program is activated a clock icon is shown on display If a clock icon is not shown on display make sure...

Страница 10: ...o exit and return to normal display any changed values will be saved Adjusting the time and day of the week Press and hold the C F Prog button the word Clock will appear on display Hours The HOURS will flash Use the and buttons to adjust the hours Minutes Press the C F Prog button again the MINUTES will flash Use the and buttons to adjust the hours Days Press the C F Prog button again the DAYS wil...

Страница 11: ...s the C F Prog button again the MINUTES will flash Use the and buttons to adjust the start time minutes of the first event Stop time Press the C F Prog button again the word Stop will appear on display The HOURS will flash Use the and buttons to adjust the stop time hours of the first event Press the C F Prog button again the MINUTES will flash Use the and buttons to adjust the stop time minutes o...

Страница 12: ...m is being set the symbols will flash Use the and buttons to adjust the start time hours of the first event Press the C F Prog button again the MINUTES will flash Use the and buttons to adjust the start time minutes of the first event System mode and fan speed Press the C F Prog button again the system MODES will flash Use the and buttons to select the system mode of the first event Press the C F ...

Страница 13: ... set points first adjusts the set point for cooling and then the set point for heating Use the and buttons to select the set point of the first event Follow the steps above for the other schedule events of the same day Prog 2 for 2 event per day or Prog 2 3 and 4 for four events per day Follow the steps above for all the other days 13 ...

Страница 14: ...w Disconnect power to the main board before installing the unit The standard height to install this unit is 1 5 meter 5 feet from the floor Installation procedure 1 separate the front display from the back plastic cover by inserting a small flat screwdriver into each of the three slots as shown in the picture and rotating it gently Keep the front display in a safe place 2 Connect the wires as show...

Страница 15: ...nal PIR See options on next pages Communication RS485 BACnet A B AO2 AO1 0 IN1 0 T1 N L 16 15 14 13 12 11 External sensor Soft start in heat sensor Deicing in cool sensor Door switch Supply 110 230VAC For T1 0 functionality refer to parameter P8 in the technician settings section For IN1 0 functionality refer to parameter P9 in the technician settings section Horizontal Top view Vertical Side view...

Страница 16: ...munication line JP2 JP3 Not in use 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 SW4 SW3 SW1 16 SW4 2 Enable Disable PIR detector OFF Enable PIR detector ON Disable PIR detector SW4 1 Without valves in FC config OFF Enable valves control ON Disable valves control SW4 3 Not in use OFF Default SW1 1 SW1 6 SW3 1 SW3 8 See pages 20 34 for different configurations ...

Страница 17: ... 2 1 1 1 1 1 2 3 2 3 2 3 2 3 2 3 14 15 1 1 2 1 1 1 16 17 18 19 2 1 1 1 1 1 1 1 1 1 1 AC Configurations index Heat elements Compressors Heat pump Fan speeds Fan VFS Economizer Humidifier Dehumidifier Reheat Dehumidify AC Configurations without humidification dehumidification AC Configurations with humidification dehumidification Configuration Outputs Configuration Outputs 17 Yes Option ...

Страница 18: ...stems without humidification dehumidification FC Configurations for 2 Pipe systems with humidification dehumidification Heat element 2nd stage Cool Heat valve Humidifier Dehumidifier Reheat Dehumidify Cool Heat valve PID Fan VFS Fan speeds Economizer Humidifier Dehumidifier Reheat Dehumidify Configuration Outputs Configuration Outputs 18 Yes Option 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 ...

Страница 19: ...ms with humidification dehumidification Heat element 2nd stage Humidifier Dehumidifier Reheat Dehumidify Fan VFS Fan speeds Economizer Floor heating Cool valve Cool valve PID Heat valve Heat valve PID Humidifier Dehumidifier Reheat Dehumidify Configuration Outputs Configuration Outputs 19 40 41 PID 42 43 44 PID PID 45 46 47 PID PID 31 32 33 34 35 36 37 38 PID PID 39 PID PID PID PID PID Yes Option ...

Страница 20: ...1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 Fan on off 110 230VAC 2 5A max Control Heat elements Heat pump Compressors Economizer 110 230VAC 0 3A max Wiring and DIP Switches AC systems 1 2 3 4 20 AO1 AO2 1 SW3 1 SW3 2 Fan speeds 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Med and High SW3 1 OFF SW3 2 OFF 2 SW3 4 HP Heat pump ON Heat pump active i...

Страница 21: ... 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 5 6 7 21 AO1 AO2 Fan VFS Fan VFS Economizer 5 option SW1 6 ON x x Economizer 5 option SW1 6 ON x x 1 SW3 1 SW3 2 Fan speeds 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Med and High SW3 1 OFF SW3 2 OFF 2 SW3 4 HP Heat pump ON Heat pump active in cool OFF Heat pump active in heat HC Not Heat pump ON Electrical heater OFF Oil Gas heater...

Страница 22: ... 2 8 7 6 5 4 3 2 1 6 5 4 3 2 1 SW3 SW1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 Fan on off 110 230VAC 2 5A max Control Heat elements Heat pump Compressors Economizer 110 230VAC 0 3A max Wiring and DIP Switches AC systems 8 9 22 AO1 AO2 2 SW3 4 HP Heat pump ON Heat pump active in cool OFF Heat pump active in heat HC Not Heat pump ON Electrical heater OFF Oil Gas heater no fan 3 SW3 5 Compressor delay ON Disable...

Страница 23: ...sor 3 8 7 6 5 4 3 2 1 6 5 4 3 2 1 Fan medium or Economizer 5 Fan high Fan low Heat element 1 2 1st stage heat Heat element 2 8 7 6 5 4 3 2 1 6 5 4 3 2 1 HP21 2 3 Speeds fan Reheat for Dehumidification Compressor 3 Heat pump 2 8 7 6 5 4 3 2 1 6 5 4 3 2 1 Fan medium or Economizer 5 Fan high Fan low Heat element 2 2nd stage heat 10 11 12 13 23 AO1 AO2 Humidifier Humidifier Humidifier 1 SW3 1 SW3 2 Fa...

Страница 24: ...0 230VAC 0 3A max Wiring and DIP Switches AC systems with Humidifier for humidification Economizer 5 option SW1 6 ON 6 5 4 3 2 1 Economizer 5 option SW1 6 ON 14 15 24 2 SW3 4 HP Heat pump ON Heat pump active in cool OFF Heat pump active in heat HC Not Heat pump ON Electrical heater OFF Oil Gas heater no fan 3 SW3 5 Compressor delay ON Disable compressor delay OFF Enable compressor delay 5 SW1 6 Te...

Страница 25: ...7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 HP11 1 Speed fan Humidifier Dehumidifier Fan 1 speed Heat pump 2 HP21 1 Speed fan Humidifier Dehumidifier Fan 1 speed Heat element 2nd stage heat 6 5 4 3 2 1 Economizer 5 option SW1 6 ON Compressor 3 Heat pump 2 Compressor 3 16 17 18 19 25 AO1 AO2 Humidifier Dehumidifier 4 Humidifier Dehumidifier 4 Humidifier Dehumidifier Humidifier Dehumidifie...

Страница 26: ... heat Heat element 2 2nd stage heat 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 20 21 22 23 26 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Medium and High SW3 1 OFF SW3 2 OFF 2 SW3 4 2nd heating stage ON Enable OFF Disable 3 SW3 5 Chilled beam option ON Enable chill...

Страница 27: ... Fan medium or Economizer 5 Fan low Heat element 2 2nd stage heat Heat element 2 2nd stage heat Heat element 2 2nd stage heat 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 24 25 26 27 27 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Medium and High SW3 1 OFF SW3 2 OFF 2...

Страница 28: ... medium or Economizer 5 Fan low Heat element 2 2nd stage heat 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 Dehumidifier Dehumidifier 28 29 30 28 AO1 AO2 x x x x x x x Economizer 5 option SW1 6 ON x 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Medium and High SW3 1 OFF SW3 2 OFF 2 SW3 4 2nd heati...

Страница 29: ...eat Fan high Fan medium or Economizer 5 Fan low Fan high Fan medium or Economizer 5 Fan low Fan high Fan medium or Economizer 5 Fan low Floor heating 1st stage heat no fan Heat element 2 2nd stage heat Floor heating 1st stage heat no fan 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 8 7 6 5 4 3 2 1 6 5 4 3 2 1 31 32 33 34 29 AO1 AO2 x x x x x x x x 1 SW3 1 SW3...

Страница 30: ...ge heat Cool valve 3 Heat valve 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 35 36 37 38 30 AO1 AO2 x x x x x x x x x Economizer 5 option SW1 6 ON x x Economizer 5 option SW1 6 ON x x Economizer 5 option SW1 6 ON x 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Medium and High SW3 1 OFF SW3 2 OFF 2 SW3 4 2nd heating ...

Страница 31: ...heat Cool valve PID 3 Heat valve PID 1st stage heat 8 7 6 5 4 3 2 1 6 5 4 3 2 1 39 31 AO1 AO2 x x 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Medium and High SW3 1 OFF SW3 2 OFF 2 SW3 4 2nd heating stage ON Enable OFF Disable 3 SW3 5 Chilled beam option ON Enable chilled beam fan will not run with cooling 5 SW1 6 Terminal 12 operati...

Страница 32: ...2 3 Speeds fan 1 Cool valve PID Reheat for Dehumidification Fan high Fan medium or Economizer 5 Fan low Heat element 2 2nd stage heat Cool valve PID 3 Heat valve 8 7 6 5 4 3 2 1 6 5 4 3 2 1 40 41 32 AO1 AO2 x x x x 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Medium and High SW3 1 OFF SW3 2 OFF 2 SW3 4 2nd heating stage ON Enable OFF...

Страница 33: ...medium or Economizer 5 Fan low Heat valve Cool valve PID 3 Humidifier 8 7 6 5 4 3 2 1 6 5 4 3 2 1 4 Pipe 1 2 3 Speeds fan 1 Heat valve PID Humidifier Fan high Fan medium or Economizer 5 Fan low Cool valve 3 Heat valve PID Humidifier 8 7 6 5 4 3 2 1 6 5 4 3 2 1 42 43 44 33 AO1 AO2 x x x x x x 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds L...

Страница 34: ...izer 5 Fan low Heat valve Cool valve PID 3 Dehumidifier 8 7 6 5 4 3 2 1 6 5 4 3 2 1 4 Pipe 1 2 3 Speeds fan 1 Heat valve PID Dehumidifier Fan high Fan medium or Economizer 5 Fan low Cool valve 3 Heat valve PID Dehumidifier 8 7 6 5 4 3 2 1 6 5 4 3 2 1 45 46 47 34 AO1 AO2 x x x x x x 1 SW3 1 SW3 2 Fan speeds 1 Speed Low SW3 1 ON SW3 2 OFF 2 Speeds Low and High SW3 1 OFF SW3 2 ON 3 Speeds Low Medium ...

Страница 35: ...or 60 seconds the thermostat will automatically exit technician settings and return to normal display Use the and buttons to make adjustments when required P01 Offset for temperature readings calibration Range 6 6 C 9 9 F Default 0 C 0 F P02 Set point limit for cooling Range 5 35 C 41 95 F Default 10 C 50 F P03 Set point limit for heating Range 5 35 C 41 95 F Default 30 C 86 F Set point limit for ...

Страница 36: ...buttons can be locked LS only and buttons cannot be locked and Can be locked and Cannot be locked P04 Enable Disable the option to lock the Fan button LF Fan button can be locked LF only Fan button cannot be locked Fan Can be locked Fan Cannot be locked Note When enabled press and hold the Mode button for 7 seconds to actually lock the buttons Note When enabled press and hold the Mode button for 7...

Страница 37: ...olarity 01 Normally open 00 Normally close Window contact Normally close Window contact Normally open In heating mode the fan will not start before there is hot water in the coil Allow deicing operation of indoor coil in cooling In 2 Pipe system T2 will sense the water temperature in the pipe in order to select allow effective system mode Where T1 terminals are used for external sensor the IN1 0 t...

Страница 38: ...e Disable Auto change over mode 00 Disable Auto change over mode 01 Enable Auto change over mode Disable Auto mode Enable Auto mode P15 Occupancy sensor logic PIR 00 Thermostat turns off when unoccupied and back on when re occupied 01 Thermostat turns off when unoccupied and remains off when re occupied 02 Thermostat uses economy set points when unoccupied 03 Un occupancy Dehumidification logic on...

Страница 39: ... PIR ON delay minutes P19 PIR Occupancy sensor polarity 00 Normally open 01 Normally close PIR Normally open PIR Normally close P18 Door switch or key tag configuration 00 Switch On or Off by door switch or key tag 01 Changing the set point temperature 02 Switching fan speed to Low Switch On or Off Change set points Switch to fan low P25 Economy set point for cooling Range 5 35 C 41 95 F Default 3...

Страница 40: ...ng stages Range 0 600 seconds Default 1 second Off delay heating stages P27 On delay time on delay between heating stages Range 0 600 seconds Default 5 seconds On delay heating stages P29 LCD Backlight ON or OFF 00 LCD Backlight ON 01 LCD Backlight OFF Backlight ON Backlight OFF P30 Beeper ON or OFF 01 Beeper ON 00 Beeper OFF Beeper ON Beeper OFF F C 40 ...

Страница 41: ...an ON delay in heating FC Only Range 0 120 seconds Default 0 seconds no delay P34 Fan OFF delay in heating Range 0 120 seconds Default 30 seconds Fan ON delay in cooling seconds Fan OFF delay in cooling seconds Fan ON delay in heating seconds Fan OFF delay in heating seconds ON OFF Fan OFF delay Fan ON delay Time sec Valve Fan P31 P34 Fan on off delay with fan on demand auto fan active 41 ...

Страница 42: ...e protection Enable freeze protection P35 Enable Disable Freeze protection 00 Disable Freeze protection 01 Enable Freeze protection F C Freeze protection cut out set point F C Note If enabled freeze protection will start when the thermostat is either ON or OFF and regardless of the current system mode The room ambient temperature which will trigger Heating ON The room ambient temperature which wil...

Страница 43: ...button to reset the filter counter The display will change from 00 to 01 and back to 00 P42 Adjust filter alarm delay time counter hours Range 0 999 hours Default 0 hours 0 Disable View filter Counter hours Adjust filter alarm delay time hours Reset filter counter The filter counter is related to Fan running time 43 ...

Страница 44: ...97 F P44 Soft start in heat cut out temperature FC Only The fan will stop if the temperature on T3 sensor drops below the cut out temperature Please refer to technician parameters P08 P09 Range 12 35 C 54 95 F Default 32 C 90 F ON OFF Fan cut in temperature Fan cut out temperature T3 Temp Heat valve Fan P43 P44 Soft start in heat with fan on demand auto fan active Soft start heat cut in temperatur...

Страница 45: ...ential band P45 P46 Cool differential band offset with cool differential band offset 0 Compressor Valve ON OFF Room Temp Set point Cool differential band Offset Cool differential band F C Cool differential band offset F C 45 P45 Cool differential band Range 0 5 5 C 1 10 F Default 1 C 2 F P46 Cool differential band offset Range 5 5 C 9 9 F Default 0 C 0 F ...

Страница 46: ...e Set point Heat differential band P47 48 Heat differential band offset with heat differential band offset 0 Compressor Valve ON OFF Room Temp Set point Heat differential band Offset F C Heat differential band offset F C 46 P47 Heat differential band Range 0 5 5 C 1 10 F Default 1 C 2 F P48 Heat differential band offset Range 5 5 C 9 9 F Default 0 C 0 F ...

Страница 47: ... 0 10 C 0 20 F Default 2 C 4 F Shift between c F C F C Shift between heating F C 47 P49 Shift between Cool and Heat in Auto mode from cooling to heating Compressor Valve Cooling ON Temp Set point Cool differential band 0 5 0 5 Shift between Cool and Heat P49 Shift between Cool and Heat in Auto mode from heating to cooling Compressor Valve Temp Set point Heat differential band 0 5 0 5 Shift between...

Страница 48: ...oportional band FC Only Range 2 10 C 4 20 F Default 2 C 4 F P56 Heat proportional low limit FC Only Range 0 100 Default 0 Heat prop low limit P57 Heat proportional high limit FC Only Range 0 100 Default 100 Heat prop high limit Cool valve proportional band F C Cool valve proportional band F C 0 10V Valve opening from fully closed to fully open Minimum valve opening Maximum valve opening 0 10V Valv...

Страница 49: ...portional ON percent P61 Fan turns OFF when the Cool or Heat valve drops below the Proportional OFF percent Fan 30 Proportional OFF percent Proportional ON percent P63 Time on delay between cooling stages AC only Range 0 600 seconds Default 5 seconds P64 Time off delay between cooling stages AC only Range 0 600 seconds Default 1 seconds Off Delay cooling stages On Delay cooling stages 49 Proportio...

Страница 50: ...ling F C 0 10V fan speed from off closed to fully running 0 10V fan speed from off closed to fully running P67 Fan VFS Low speed percent in cooling Range 0 30 Default 20 P68 Fan VFS Medium speed percent in cooling Range 30 60 Default 50 P69 Fan VFS High speed percent in cooling Range 60 100 Default 90 P70 Fan VFS Low speed percent in heating Range 0 30 Default 30 VFS Low in cooling VFS Med in cool...

Страница 51: ...g High 50 Fan VFS Med speed percent In cooling 90 Fan VFS High speed percent In cooling Fan VFS High speed diff 90 35 55 Fan VFS Medium speed diff 50 35 15 P74 VFS Medium speed differential display from medium to low P75 VFS High speed differential display from high to medium Speed on display P74 VFS Medium speed differential Range 10 50 Default 35 P75 VFS High speed differential Range 10 50 Defau...

Страница 52: ... 0 P77 Fan VFS High limit in cooling Range 0 100 Default 100 P78 Fan VFS Low limit in heating Range 0 100 Default 0 P79 Fan VFS High limit in heating Range 0 100 Default 100 VFS low limit in cooling VFS high limit in cooling VFS low limit in heating VFS high limit in heating 52 ...

Страница 53: ...nly Range 9 5 8 C 15 46 F Default 0 C 32 F P86 Deice in cool cut out temperature AC only Range 2 20 C 36 68 F Default 8 C 46 F Deice in heat time Deice in heat break time Deice in cool F C Deice in cool F C The indoor unit coil temperature in which deicing will stop The indoor unit coil temperature in which deicing will start The length of deicing procedure The time interval between deicing cycles...

Страница 54: ... for cooling and heating 01 two set points one for cool and one for heat One set point Two set points P98 Display set point only hide room temperature 00 Display both set point and room temperatures 01 Display only the set point temperature Hide room temperature Compressor delay Deice in heat F C Deice in heat F C Show room temperature The outdoor unit coil temperature in which deicing will stop T...

Страница 55: ...aturday and another for Sunday 04 7 days with the different program for each day P108 Weekly program events per day 00 Two different events per day 01 Four different events per day P109 Weekly program event configuration 00 US Program Event start time Mode Fan speed Set points one or two 01 Eu program Event start time Stop time Screen dimming delay Weekly program configuration Weekly program event...

Страница 56: ...Only Range 0 100 Default 0 P118 Cool PID Kd FC Only Range 0 100 Default 1 P119 Heat PID Kd FC Only Range 0 100 Default 1 P114 Cool PID Kp FC Only Range 0 100 Default 100 P115 Heat PID Kp FC Only Range 0 100 Default 100 Cool PID Kp Heat PID Kp Cool PID Ki Heat PID Ki Cool PID Kd Heat PID Kd 56 ...

Страница 57: ...C Only Range 0 100 seconds Default 60 seconds Cool proportional threshold time Heat proportional threshold time Display or hide humidity readings 57 P160 Minimum compressor ON time AC Only Range 0 20 minutes Default 2 minutes Min compressor ON time P161 Minimum compressor OFF time AC Only Range 0 20 minutes Default 13 minutes Min Compressor OFF time P170 Economizer low limit temperature Range 9 27...

Страница 58: ...eheat in unocc mode Display switching time Hum Temp Humidity differential band P189 Dehumidification cycle in unoccupied mode Range 0 600 minutes Default 20 minutes P190 Dehumidification break time in unoccupied mode Range 0 900 minutes Default 40 minutes Dehumidification cycle in unocc mode Dehumidification break in unocc mode 58 F C P188 Room temperature limit for disabling dehumidification in u...

Страница 59: ...ion Range 0 100 RH Default 0 RH P197 Humidity set point Range 20 100 RH Default 45 RH Dead zone Hum Dehum Humidity set point P200 Restore defaults Press the button the display will change from 00 to 01 Press the On Off button to restore default settings The thermostat will turn Off 59 P195 Humidity sensor reading offset Range 9 9 RH Default 0 RH Humidity offset Restore defaults ...

Страница 60: ...to enter MAC Address configuration mode Use the or buttons to define the MAC Address range 1 127 When finished press the On Off button and Readjust he set point Warning Do not use the same MAC address for two devices on the same communication line Important In order for the MAC address changes to take effect switch power supply off and on MAC Address 1 127 60 ...

Страница 61: ...er in cool indication Deicer in heat indication Overheat in heat Overheat in cool Teconomizer sensor fault Economy by Built in External PIR Communication Economy by door switch Economy by Window contact Remote on off switch Window contact Remote economy switch Economy by key tag ...

Страница 62: ...Notes 62 ...

Страница 63: ...Notes 63 ...

Страница 64: ...Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com www meitavtec com ...

Отзывы: