Technician Settings (Cont’)
P13 – Door switch delay time
Range: 0…999
seconds.
Default: 180
seconds.
Door switch
delay time (sec.)
P11 – Window contact delay time
Range: 0…999
seconds.
Default: 600
seconds.
Window contact
delay time (sec.)
P12 – Door switch (terminals T1,0) polarity
“01” - Normally open
“00” - Normally close
Door switch
Normally close
Door switch
Normally open
P14 – Enable/Disable Auto change over mode
“00” - Disable Auto change over mode
“01” - Enable Auto change over mode
Disable
Auto mode
Enable
Auto mode
P15 – Occupancy sensor logic (PIR)
“00” - Thermostat turns off when unoccupied
and back on when re-occupied.
“01” - Thermostat turns off when unoccupied
and remains off when re-occupied.
“02” - Thermostat uses economy set points
when unoccupied.
“03” - Un-occupancy – Dehumidification logic.
(only available with dehumidification configuration
– see DIP swich settings)
Unocc. – Off
Re-occ. - On
Unocc. – Off
Re-occ. - Off
Economy
set points
Dehumidification
logic
- 38 -