eißner gate systems 7 - 4
Gate control operating manual mts2000/02
Maintenance & service
Measurement points and values for control PCB, pins 63 – 71
Test
specimen
Measurem.
point 1
Measurem.
point 2
Measurem.
parameter
Measurem.
result
Unit Condition
Voltage
+/- 10%
24 VDC
Impulse outside or closed
impulse activated (contact
closed)
Impulse
outside and/or
closed
impulse
69 63
Voltage 0 VDC
Impulse outside or closed
impulse not activated (contact
closed)
Voltage
+/- 10%
24 VDC
Impulse inside or open impulse
activated (contact closed)
Impulse
inside and/or
open impulse
70 63
Voltage 0 VDC
Impulse inside or open impulse
not activated (contact closed)
Voltage
+/- 10%
24 VDC
Impulse for halt and stop not
activated (contact closed)
Impulse for
halt
71 63
Voltage 0 VDC
Impulse for halt and stop
activated (contact open)