4
m
eißner gate systems
4 - 10
Gate control operating manual mts2000/02
Description of product
4.6.3
Stop in closed position (passage protection)
4.6.3.1 Process of re-opening after triggering during closing.
During the closing process, the gate will open to its limit position if the passage
protection is triggered.
Note
This applies to all operating modes.
4.6.3.2 Hold open time
If the function is set to “NO” for "Reset hold open time via passage protection“ (also
refer to option for "RESET O TIME VIA PP" in Chapter "Program gate" 6.1.4), the
time expires despite the passage protection being triggered.
Note
This applies to the single lane and dual lane feedback control operating modes.
4.6.3.3 Extending the hold open time
The hold open time is restarted by triggering the passage protection before the hold
open time lapses after opening the gate and reaching the top limit position. The
hold open time can be set to anything between 1 and 600 seconds.
Note
This applies to the single/dual lane feedback control operating modes.